18
PACIFIC FP30 190712-28
18" [457mm]
8" [203mm]
8" [203mm]
19 1/8"
[486mm]
18" [457mm]
8" [203mm]
8" [203mm]
58" [1.47m]
Canada Only
Floor Protector
The stove may be installed on a combustible fl oor provided
non-combustible ember protection, such as tile, metal, brick,
etc., is used in front of the unit as per Fig. #16 & #17.
This protection must extend as follows:
In Canada: 18" (457 mm) on the fi ring side and 8" to the
sides. See Figure #16, below.
U.S.A. Only
Non-combustible
fl oor protector
FIG. #16
FIG. #17
In U.S.A: 18" (457 mm) to the front and 8" to the sides of the
fuel loading door opening. See Figure #17, below.
Minimum Width - 58"
Minimum Overall Depth - 18"
Non-combustible
fl oor protector
Minimum Width - 38.5"
Minimum Overall Depth - 19 1/8"
Safety Strip
The fl oor between the fi replace and the hearth extension/
ember protection must be protected with a safety metal strip.
One half of the metal strip must be under the fi replace front
and the other half must extend onto the fl oor and under the
hearth extension/ember protection as shown in Fig. #18.
Safety metal strip
Cement Board 1/2”
minimum(if desired)
Hearth extension
non-combustible
finish material
Floor
The space between
the fireplace and the
hearth extension must
be sealed with a
non-combustible
material such as
sand-cement grout.
Fireplace front
FIG. #18
Blower Wiring
The FP30 must be connected 120 VAC house hold electrical
system.
It is recommended to also connect the unit to a wall switch
or fan speed controller.
Insert the Nomex 14/2 wire, or equivalent, into the unit
through the strain relief located on the right hand side of the
fi replace casing.
Connect the wiring as shown in the wiring diagram below to
the terminal block located in the bottom of the unit. See section
(Blower Repair) on Page 7. All electrical connections should
be performed by a certifi ed/licensed electrician.
110VAC COMMON
GROUND
110VAC SWITCHED
Blower
Thermo
Switch
Electrical Rating : 115 V, 60 Hz, 1.1A
120412
5050.7434
MALE/FEMALE
CONNECTION
TERMINAL
BLOCK