12
040515-24
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
FIG. #8
Chimney
Roof fl ashing
Storm collar
* 4" diameter air inlet with rodent screen
* If the crawl space is well ventilated
it is not necessary to extend air inlet to
outside
Spark arrestor
rain cap
Radiation shield
Chimney Connector
Chimney Support
47.5" (1207 mm)
Minimum
Minimum 7' (2.1m.)
Ceiling Height
Attachment to fl oor for
mobile homes
Non-combustible
fl oor protector
48"
(1219 mm)
3' (914 mm)
Minimum
Hooded vent or
90 elbow turned down
The chimney may incorporate
an offset. To do this safely, all
sections of listed connector,
offset elbows and chimney
section must be screwed
together by at least three
sheet metal screws per joint.
The chimney must be suitably
supported by the chimney
manufacturer's listed offset
support.
Procedure:
CAUTION: THE STRUCTURAL INTEGRITY OF THE MO-
BILE HOME FLOOR, WALL AND CEILING/ROOF MUST
BE MAINTAINED.
- The services of a competent or certifi ed installer, (certifi ed
by the Wood Energy Technical Training program (WETT) - in
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,)
are strongly recommended.
Note: See "Combustion Air" section on page 10.
1. Position stove and fl oor protection with hole for combus-
tion air in accordance with the clearances as stated on
the label and in Figure #7.
2. Mark the position for the hole in the ceiling and roof by
using a string and plumb-bob.
3. Check that the intended location will not interfere with fl oor
joists, ceiling joists or rafters before proceeding further.
4. Cut a hole in the ceiling and roof to suit the chimney
system and frame in the sides. The chimney support is
mounted to the framing.
5. If the chimney connector exits the mobile home less then
7 feet above the ground then a guard must be installed
to cover the connector up to a height of 7 feet(2.13m).
6. The guard must not have opening larger than 3/8"(10mm)
and must maintain a space of 4"(102mm) minimum around
the chimney
connector.
7. Assemble chimney sections so the fi nished length is rest-
ing on the support and protruding through the roof. Avoid
having joints between ceiling and roof. Install radiation
shield. Assemble fl ashing and storm collar and be sure to
maintain the vapour barrier at this point. (Seal securely.)
Attach rain cap and check fl ashing for leaks.
8. Install connector as per manufacturer's instructions.
9. Attach stove to fl ooring using two 1/4" x 2" or longer lag
screws.
Alternate up and
out installation
12"(305mm)
Minimum fi rst
section of pipe.
12"(305mm)
Minimum
Wall Thimble
Unit may be harder to start.
Please provide as much verti-
cal length for the fi rst section
of pipe as possible.
*
*