background image

12  

040515-24

©PACIFIC ENERGY FIREPLACE 
PRODUCTS LTD.

 

FIG. #8

Chimney

Roof fl ashing

Storm collar

*  4" diameter air inlet with rodent screen
*  If the crawl space is well ventilated 
it is not necessary to extend air inlet to 
outside

Spark arrestor 
rain cap

Radiation shield

Chimney Connector

Chimney Support

47.5" (1207 mm)

Minimum

Minimum 7' (2.1m.)

Ceiling Height

Attachment to fl oor for
mobile homes

Non-combustible
fl oor protector

48"

(1219 mm)

3' (914 mm)

Minimum

Hooded vent or
90 elbow turned down

The chimney may incorporate 
an offset.  To do this safely, all 
sections of listed connector, 
offset elbows and chimney 
section must be screwed 
together by at least three 
sheet metal screws per joint.  
The chimney must be suitably 
supported by the chimney 
manufacturer's listed offset 
support.

Procedure:

CAUTION: THE STRUCTURAL INTEGRITY OF THE MO-
BILE HOME FLOOR, WALL AND CEILING/ROOF MUST 
BE MAINTAINED.

- The services of a competent or certifi ed installer, (certifi ed 
by the Wood Energy Technical Training program (WETT) - in 
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,) 
are strongly recommended.

Note: See "Combustion Air" section on page 10.

1.  Position stove and fl oor protection with hole for combus-

tion air in accordance with the clearances as stated on 
the label and in Figure #7.

2.  Mark the position for the hole in the ceiling and roof by 

using a string and plumb-bob.

3.  Check that the intended location will not interfere with fl oor 

joists, ceiling joists or rafters before proceeding further.

4.  Cut a hole in the ceiling and roof to suit the chimney 

system and frame in the sides. The chimney support is 
mounted to the framing.

5.  If the chimney connector exits the mobile home less then 

7 feet above the ground then a guard must be installed 
to cover the connector up to a height of 7 feet(2.13m).

6.  The guard must not have opening larger than 3/8"(10mm) 

and must maintain a space of 4"(102mm) minimum around 
the chimney 

 connector.
7.  Assemble chimney sections so the fi nished length is rest-

ing on the support and protruding through the roof. Avoid 
having joints between ceiling and roof.  Install radiation 
shield. Assemble fl ashing and storm collar and be sure to 
maintain the vapour barrier at this point. (Seal securely.) 
Attach rain cap and check fl ashing for leaks.

8.  Install connector as per manufacturer's instructions.
9.  Attach stove to fl ooring using two 1/4" x  2" or longer lag 

screws.

Alternate up and 
out installation

12"(305mm)

Minimum fi rst

section of pipe.

12"(305mm)

Minimum

Wall Thimble

Unit may be harder to start. 
Please provide as much verti-
cal length for the fi rst section 
of pipe as possible.

*

*

Содержание NEO 1.6 INSERT

Страница 1: ...tructions Contact local building or fire officials about restrictions and installation inspection requirements in your area TESTED and LISTED to CAN ULC S627 AND UL 1482 Meets the Environmental Protection Agency s May 2015 Particulate Emission Standards IMPORTANT THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOMEOWNER MODEL NEO 1 6 SERIES A SERIAL PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2014 ...

Страница 2: ...als about restrictions and installation inspection requirements in you area Please read this entire manual before you install and use your new room heater Failure to follow instructions may result in property damage bodily injury or even death Contents Safety 3 Chimney Smoke and Creosote Formation 3 Chimney Fires 3 In Case of a Chimney Fire 3 Avoiding a Chimney Fire 3 Operation 4 Wood Selection 4 ...

Страница 3: ...ust be lived with Regular inspection and cleaning is the solution The use of dry seasoned wood and am ple combustion air will help to minimize annoying smoke emissions and creosote buildup Chimney Fires The result of excessive creosote buildup is a chimney fire Chimney fires are dangerous Chimney inside temperatures can exceed 2000 F 1100 C This causes much higher than normal temperatures in the c...

Страница 4: ...re than one side within one minute It is damp if it turns black and lights within three minutes If it sizzles hisses and blackens without igniting in five minutes it is soaked and should not be burnt Lighting a Fire WARNING Never use chemicals or any other volatile liquid to start a fire 1 Adjust air control to High position all the way to the left and open door 2 Place crumpled newspaper in the c...

Страница 5: ...r other stove lighting devices within the pedestal area Although this is possible it is not recommended NOTE Refer to local fire codes CAN B365 and NFPA 211 in the U S WARNING IFYOU CHOOSETO STOREWOOD BENEATH YOURUNIT EXERCISEEXTREMECAUTIONWHENLOAD ING THE WOODSTOVE EMBERS CAN FALL AND MAY IGNITE WOOD BENEATH STOVE WARNING No alteration or modification of the combus tion air control assembly is pe...

Страница 6: ... from your dealer Use 16 1 2 419mm x 10 1 2 267mm x 5 mm Ceramic glass only Do not substitute with any other type To remove broken glass remove the door gasket and then undo the eight screws securing the gasket guides and glass retainers Remove all particles of glass Be careful as they are very sharp Install new glass complete with gasket Re place glass retainers and gasket guides then install new...

Страница 7: ...Air riser tube in the back of the firebox Back side of airwash chamber located in the upper front of firebox Baffle locking pin Boost tube cover located in center of manifold bottom front of firebox When Cleaning the Chimney System Top baffle board blanket Baffle Brick Rails Manifold located in bottom front of firebox Blower The blower should be cleaned out a minimum every six months by using a va...

Страница 8: ... 3 Usinga7 16 12mm wrench removelagboltsthatsecure hold down brackets to bottom pallet 4 Slide the hold down brackets away from the stove Side Panel Installation 1 Carefully remove the panels from the box 2 Engage the tabs in the panel into the slots in the panel mounting bracket Fig 1 3 Attachthepanel totherearshield Securewithtwoscrews Fig 2 FIG 1 SCREWS Assembly NOTE DIMENSION DOES NOT INCLUDE ...

Страница 9: ...t To draw outside air from behind the stove an outside air adaptor may be required see Optional Blower section Cut or drill a 4 102mm hole through a wall behind the unit Use an appropriate household 4 102mm inlet Note This unit is not designed to be operated with the firing door open In addition to the obvious hazard of sparks landing on combustibles an open fire door will cause the heater to draw...

Страница 10: ...ing codes The chimney flue size should be the same as the stove outlet for optimal performance Reduc ing or increasing the flue size may adversely affect stove performance Chimney flue exit is to be 3 feet 1 m above roof and two feet 0 6 m above highest projection within 10 feet 3 m The installation must meet all local codes Do not connect this unit to a chimney flue serving another appliance Mini...

Страница 11: ...STED CONNECTOR AND CHIMNEY AND CHIMNEY Outside air supply must be used for Mobile Home installa tions see Figure 8 Page 13 Remove the chimney down to the roof flashing to allow for transportation of the mobile home FIG 6 Double Wall Connector Residential Single Wall Connector Residential Alcove Min Height 7 Max Depth 3 Double Wall Connector Mobile Home Clearances This heater must be installed with...

Страница 12: ...n air in accordance with the clearances as stated on the label and in Figure 7 2 Mark the position for the hole in the ceiling and roof by using a string and plumb bob 3 Checkthattheintendedlocationwillnotinterferewithfloor joists ceiling joists or rafters before proceeding further 4 Cut a hole in the ceiling and roof to suit the chimney system and frame in the sides The chimney support is mounted...

Страница 13: ...inimum 7 2 1m Ceiling Height Non combustible floor protector 48 1219 mm Hooded vent or 90 elbow turned down Ensure that the Masonry chimney meets all National Fire Protection Association and local building codes Have the chimney cleaned and inspected by a professional to ensure there are no cracks weak mortar or other signs of deterioration See pipe manufactuers installation instructions for furth...

Страница 14: ...the fire has gone out and the unit cooled to below a useful heat output range Manual Tomanuallyoperatetheblower settherockerswitch to Man and set the speed control to desired setting This will bypass the sensing device and allow full control of the blower Switching from Auto to Man or selecting speed may be done anytime Optional Outside Air Adaptor The adaptor OAIR 1A is only required if outside c...

Страница 15: ...ted check flue Provide outside air for combustion 4 Door gasket leakage Replace gasket Check latch Excessive Creosote Buildup See 1 2 3 above Low Heat Output 1 Wood is wet Use dry wood 2 Fire too small Build a larger fire 3 Draft too low Chimney plugged or restricted inspect and clean Stove Won t Burn 1 Combustion air supply blocked Check outside air supply for obstruction Check that room air cove...

Страница 16: ...ment Baffle Kit NE16 BAFKIT 15 Baffle Pin SSER 125001 16 Ash System NE16 LGADA 17 Left Support Black NE16 78115 17b Right Support Black NE16 78125 18 Ash Dump Assembly NE16 7857 19 Ash Drawer NE16 78352 20 Air Shutter Assembly NE16 7826 21 Secondary Air Control Assembly NE16 7833 22 Trivet NE16 5037704 23 Levelling Feet 4pcs NE16 5049765 24 Lower Grill Assy NE16 5037703 25 Upper Grill NE16 5037702...

Страница 17: ...erstanding the basic functions of this design Traditionalwoodstoveshadabasiccombustionsystemwhich allowed a considerable amount of heat energy to escape up the chimney as unburned gases and particulates smoke Pacific Energy has designed a system that solves the prob lem by burning the smoke and releasing the additional heat to the room Thissystemhastwocriticaldesign features 1 Above fire secondary...

Страница 18: ... x 32 mm 5096 99 NEO 1 6 Firebrick Installation Instructions This package contains 13 full size firebricks as well as 2 various cut size bricks With the heater in the upright position install firebricks as follows Place 4 full size firebricks at the back of the heater first Next install the side firebricks 3 full size each side as shown below Lastly install 3 full size firebricks and bricks A B as...

Страница 19: ...s operating correctly at installation Any part that shows in our judgment evidence of defect shall be repaired replaced or refunded at Pacific Energy s option The defective part may be required to be returned to Pacific Energy or an accredited agent transportation prepaid Porcelain is warranted for gloss retention Certain colors may darken when heated and return to the original shade when cool Gla...

Страница 20: ...20 040515 24 PACIFIC ENERGY FIREPLACE PRODUCTS LTD ...

Страница 21: ...040515 24 21 PACIFIC ENERGY FIREPLACE PRODUCTS LTD ...

Страница 22: ...22 040515 24 PACIFIC ENERGY FIREPLACE PRODUCTS LTD ...

Страница 23: ...ES INSTRUCTIONS D INSTALLATION ET D OPÉRATION FOURNI AVEC L APPAREIL CONTACTEZ LES OFFICIELS DE LA CONSTRUCTION OU DE SERVICE D INCENDIE POUR DES INFORMATIONS QUANT AUX RESTRICTIONS PERMIS D INSTALLATION ET INSPECTIONS DANS VOTRE RÉGION NE RELIEZ PAS CET APPAREIL À UN CONDUIT DE CHEMINÉE DESSERVANT DÉJÀ UN AUTRE APPAREIL ÉTATS UNIS SEULE MENT UTILISEZ UN RACCORDEMENT NOIR OU CLASSÉ DE 24 MSG ET AV...

Страница 24: ...C ENERGY FIREPLACE PRODUCTS LTD PACIFIC ENERGY FIREPLACE PRODUCTS LTD 2975 Allenby Rd Duncan B C V9L 6V8 For technical support please contact your retailer Web site http www pacificenergy net Printed in Canada ...

Отзывы: