
040515-24
11
©PACIFIC ENERGY FIREPLACE
PRODUCTS LTD.
18"
457mm
12"
305mm
25 1/2”
673mm
20"
508mm
8"
203mm
11"
279mm
5"
127mm
15"
381mm
3"
8"
203mm
3"
76mm
8"
203mm
8"
203mm
21 1/2"
549mm
8"
203mm
11"
279mm
5"
127mm
21 1/2"
549mm
15"
381mm
21 1/2"
549mm
8"
203mm
11"
279mm
5"
127mm
3"
76mm
3"
76mm
Mobile Home
Minimum
Clearance to
Combustibles
Warning:
Under no circumstances is this heater to be installed
in a makeshift or "temporary" manner. It may be fi red only
after the following conditions have been met.
-
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
-
DO NOT INSTALL IN A SLEEPING ROOM.
- BOTH CHIMNEY SYSTEM AND CONNECTOR MUST BE
LISTED TO: IN CANADA - ULC S-641 LISTED CONNEC-
IN CANADA - ULC S-641 LISTED CONNEC-
TOR AND ULC-S-629 LISTED CHIMNEY,
TOR AND ULC-S-629 LISTED CHIMNEY,
IN USA - UL-103 HT LISTED CONNECTOR
IN USA - UL-103 HT LISTED CONNECTOR
AND CHIMNEY
AND CHIMNEY
- Outside air supply must be used for Mobile Home installa-
tions see Figure #8, Page 13.
- Remove the chimney down to the roof fl ashing to allow for
transportation of the mobile home.
FIG. #6
Double Wall Connector - Residential
Single Wall Connector - Residential
Alcove: Min. Height 7'
Max. Depth 3'
Double Wall Connector - Mobile Home
Clearances
This heater must be installed with a listed double-wall con-
nector and compatible chimney system.
Clearances to combustible surfaces and materials are shown
in Figure #7 below.
Clearances may be reduced with various heat insulating ma-
terials. Consult local fi re codes and authorities for approval.
NOTE:
Longer chimney lengths and different pitch fl ashings
may be used. All other parts listed must be installed (see
Figure #8, Page 13). Install all components to the connector
or chimney manufacturer's installation requirements. Consult
your chimney supplier for installation advice.
Residential
Minimum
Clearance to
Combustibles
FIG. #7
Mobile Home Installation