VENTING

Before installing venting for this unit, the installer should read these
instructions to ensure that the proper vent configuration has been
selected.
Use only Pacific Energy vent kits #:

GASC.WALKIT - Wall Termination Kit
ESTD.ROTKIT - Roof Termination Kit
ESTD.VP05 - 5' Vent Pipe Kit
ESTD.VP10 - 10' Vent Pipe Kit

Standard roof flashing or flashing listed below may be used.

ESTD.ROFLAT - Flat Roof Flashing (flat roof)
ESTD.ROADJ - Adjustable Roof Flashing (1/12 to 7/12 pitch)
ESTD.ROSTP - Steep Roof Flashing (8/12 to 12/12 pitch)

Vent system components approved for use with the Estate Fireplace
are shown in Figure # 9 and Appendix A.  The Estate Fireplace is also
tested and certified for use with SIMPSON DURA-VENT DIRECT
VENT GS pipe (see Optional Venting section).
NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE
USED.
Various combinations of vertical and horizontal runs may be used.
Refer to Figures # 8d, 8e, & 8g for details.  For optimum performance
and flame appearance, keep the vent length to a minimum.  Connec-
tions between each vent system component must be tightly joined
and sealed, and secured with sheet metal screws at each joint.  A
horizontal run of vent must have a 1/4" rise for every 2 ft.of run towards
the termination.

NOTE:  The minimum top exit vent
length is a combination of 16" rise
and 14" run.  For longer venting
configurations, the rise and run
must be constrained to the bounda-
ries of this chart.

VERTICAL RISE

HORIZONTAL RUN

PACIFIC ENERGY

WALL TERMINATION VENTING

Fig. # 8d

NOTE:  At 31 1/2" up, the maxi-
mum horizontal rear exit vent
length is 18" with a 45° elbow
(see below).

CAUTION:  UNDER NO CONDITION SHOULD COMBUSTIBLE
MATERIAL BE CLOSER THAN 1 INCH FROM THE VERTICAL
AND HORIZONTAL SECTIONS OF THE PACIFIC ENERGY VENT
SYSTEM OR 1-3/4 INCHES FROM THE SIMPSON DURA-VENT
DIRECT VENT GS SYSTEM.

Exterior wall opening:

IMPORTANT: Before cutting an opening in an exterior wall, ensure
correct vent terminal location by referring to the clearance specifica-
tions noted on Figure #13.

It is preferred to cut an opening between two building framing
members to avoid any extra framing.  Consult your local building
codes prior to proceeding.  The vent kit will accommodate a maximum
wall thickness of 11-1/2 inches.

Having determined the vent terminal location, cut and frame an
opening of 10-1/2 inches.  The opening may be round or square.
Minimum distance from the finished floor to the centre of the opening
in a flat wall is 52 inches, and 59-1/4 inches in a corner installation for
top vent, or 31 1/2" for rear vent.  Height of the opening will vary with
each installation.  As the horizontal vent run increases, so does the
minimum vertical rise.

NOTE:  The vent must not exceed
a total length of 20 feet.  Any
combination of rise and run may
be used but must be constrained
to the boundaries of this chart.  For
each additional 90° elbow, reduce
vent length by 2 feet.  For each
additional 45° elbow, reduce vent
length by 1 foot.

18"

1’

2’

3’

4’

5’

18"

31 1/2"

f i r e - p a r t s . c o m

Содержание G Series

Страница 1: ...plier s instructions Ifyoucannotreachyourgassupplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier FOR YOUR SAFETY IMP...

Страница 2: ...TIONAL VENTING 16 OPTIONAL SNORKEL VENT TERMINAL 19 MANUFACTURED MOBILE HOME 20 GAS SUPPLY 20 WALL SWITCH OR THERMOSTAT 20 BURNER REMOVAL 21 OPTIONAL BRICK PANELS INSTALLATION 21 EMBER MATERIAL INSTAL...

Страница 3: ...n Do not use this heater if any part has been under water Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which...

Страница 4: ...ces on the following page and the Screen Front Framing Section Minimum Clearances to Combustibles Side standoffs 0 in 0 mm Back standoffs 0 in 0 mm Top standoffs 0 in 0 mm Adjacent sidewall 6 in 152 m...

Страница 5: ...wall or chase it is recommended that the outer walls be insulated to same degree as other exterior walls Do not place the fireplace directly against the insulation Cover the insulation and plastic va...

Страница 6: ...vent system is installed Heavier construction may be required for some Fig 7 Fig 6 Fig 5 Fig 4 NAILING TABS CORNER FRAMING DIMENSIONS FRAMING DIMENSIONS Examples of Common Installation Locations insta...

Страница 7: ...eplace to framing with screws or nails see Fig 4 The tabs will allow for a finishing wall up to 3 4 inch thick if thicker unit must be spaced outwards accordingly Due to higher temperatures with the S...

Страница 8: ...op vent outlet 4 Secure in place with screws previously removed see Fig 8b Fig 8a Black Sealant VENT ADAPTER INSTALLATION The Estate fireplace easily adapts to use either the Pacific Energy Flex Vent...

Страница 9: ...nd run mustbeconstrainedtothebounda ries of this chart VERTICAL RISE HORIZONTAL RUN PACIFIC ENERGY WALL TERMINATION VENTING Fig 8d NOTE At 31 1 2 up the maxi mum horizontal rear exit vent length is 18...

Страница 10: ...llation location of the restrictor see Fig 21 Remove the glass front and the two rear logs Remove the one top mounting screw shown in Fig 8f place the restrictor over the hole and replace the one scre...

Страница 11: ...t maximum 2 foot intervals see Fig 10 Spacers may have to be closer if pipe is bent 90 1 Bend pipe spacer around the 4 inch inner pipe With endsofspaceroverlapped bendlockingtabsintoplace see Fig 10 2...

Страница 12: ...ntervals see Fig 9 Spacers may have to be closer if pipe is bent 90 The vent system must be supported approximately every 3 feet Use pipe support straps provided with kit to maintain a 1 inch clearanc...

Страница 13: ...nded above meter regulator assembly AIR SUPPLY INLET VENT TERMINAL GAS METER FIXED CLOSED FIXED CLOSED OPERABLE OPER ABLE INSIDE CORNER DETAIL AREA WHERE TERMINAL IS NOT PERMITTED Canadian Installatio...

Страница 14: ...d the 8 inch outer flex pipe through the roof opening Slip the flex pipe a minimum of 1 1 2 inches over the support sleeve Secure pipe to the sleeve with screws provided Seal the joint and screw heads...

Страница 15: ...m of 1 1 2 inches over the inner collar of the roof vent terminal Secure to the collar with screws provided Seal the joint and screw heads using the high temperature sealant provided 8 Lower the roof...

Страница 16: ...1 3 4 INCHES FROM ANY VERTI CAL AND HORIZONTAL VENT SECTIONS OF THE SIMPSON DURA VENT DIRECT VENT GS SYSTEM Fig 19b WALL TERMINATION TOP VENTING DURA VENT GS VERTICAL RISE HORIZONTAL RUN 1 2 3 4 5 1...

Страница 17: ...ot ex ceed a total length of 40 feet Any combination of rise and run may be used but must be constrained to the boundaries of this chart Foreachadditional 90 elbow reduce vent lengthby2feet Foreach ad...

Страница 18: ...his minimum vertical rise a maximum horizontal run of 18 is permitted For longer horizontal runs the vertical rise must also increase The rise and run must be constrained to the boundries of the chart...

Страница 19: ...connect the Dura Vent GS Snorkel Termination to the Estate flexible vent an Estate Snorkel Adaptor ESTD SNADPT is required 1 Attach the Estate Snorkel Adaptor to the Snorkel Terminal see Fig 19g 2 Ex...

Страница 20: ...immediately upstream of the gas supply connection to the appliance Correct gas pressure requirement Natural Gas Propane Min Pressure 5 0 wc 12 5 wc For purpose of input adjustment Max Pressure 10 5 w...

Страница 21: ...and set aside taking care not to damage them Remember the logs are extremely fragile Remove ember material and save for reuse 4 Disconnect gas supply line 5 Remove the two wing nuts under the firebox...

Страница 22: ...ve the grate by removing four attach ment screws shown in Figure 23 Place the Platinum Bright Embers adjacent to the burner ports creating a channel as shown below Place the Glowing Embers randomly on...

Страница 23: ...pins should have washers installed on them These washers are required to support the logs Place the coal chunk and the remaining logs as shown in Figures 23 26 Note Improper placement of logs may caus...

Страница 24: ...lt the blower on its side and slide it past the left side of the gas valve Position the blower onto the studs located at the rear of the fireplace The studs must protrude through the front rubber grom...

Страница 25: ...anual is not followed a fire may result causing PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE Unpack and inspect the Screen Door A flathead Phillips or a 2 Robertson screwdriver is required to insta...

Страница 26: ...l your service technician or gas supplier 9 Turn gas control knob counter clockwise to On position 10 Turn HI LO burner control knob to desired setting 11 Close bottom grill and turn on the burner swi...

Страница 27: ...o a desired setting As heat is required in the room the fireplace will turn on or off automatically Extend Shutdown To shutdown the appliance including the pilot partially depress and turn gas control...

Страница 28: ...ASSEMBLY ESTF 3700 3 PANEL RIGHT OR LEFT SIDE 5098 403 4 PANEL BACK 5098 402 5 REPLACEMENT GLASS 5034 3 6 WINDOW GASKET KIT ESTD 50671 7 GLASS FRAME ESTG 17265 8 OVERLAY TRIM Standard ESTD STDO Radian...

Страница 29: ...ASSEMBLY ESTF 3705 11 IGNITER 5016 5 12 ANDIRON ASSEMBLY ESTF 2822 13 VENTURI TUBE ASSEMBLY ESTF 501131A 14 VENTURI TUBE GASKET 5068 1012 15 MANIFOLD 5012 5 16 NG BURNER ORIFICE 39 5021 33 LP BURNER...

Страница 30: ...he slots in the upper brackets see Fig 1 2 Fasten bottom louver to the hinge brackets at the bottom of the appli ance see Fig 2 Fig 1 This kit contains 1 Top Louver 1 Bottom Louver 6 8 x 1 2 sheet met...

Страница 31: ...l Roof Thimble 1 4 1 2 Pipe Clamp Wall Termination Kit GASC WALKIT This vent kit is for use with these models The ESTATE and The ESTEEM fireplaces Please refer to the Installation Instructions provide...

Страница 32: ...Sealant 1 Mastic 1 Roof Vent Terminal 1 Wall Roof Thimble 1 Support Sleeve 1 Storm Collar 2 Roof Brackets Roof Termination Kit ESTD ROTKIT This vent kit is for use with these models The ESTATE and The...

Страница 33: ...and The ESTEEM fireplaces Please refer to the Installation Instructions provided with the appliance for proper venting installation This box contains 3 Pipe Spacer 2 8 x 1 2 sheet metal screws 8 10 x...

Страница 34: ...Please refer to the Installation Instructions provided with the appliance for proper venting installation This box contains 10 4 Flex Vent 10 8 Flex Vent 1 4 Vent Connector 1 8 Vent Connector 1 Fires...

Страница 35: ...l dans une maison pr fabriqu e mobile install e demeure si les r glements locaux le permettent Voir la notice du propri taire pour plus de d tails Cet appareil ne peut tre converti d autres gaz sauf s...

Страница 36: ...36 Pacific Energy Fireplace Products Ltd PO Box 1060 Duncan B C V9L 3Y2 Phone 250 748 1184 Web site www pacificenergy net Printed in Canada fire parts com...

Отзывы: