VENTING
Before installing venting for this unit, the installer should read these
instructions to ensure that the proper vent configuration has been
selected.
Use only Pacific Energy vent kits #:
GASC.WALKIT - Wall Termination Kit
ESTD.ROTKIT - Roof Termination Kit
ESTD.VP05 - 5' Vent Pipe Kit
ESTD.VP10 - 10' Vent Pipe Kit
Standard roof flashing or flashing listed below may be used.
ESTD.ROFLAT - Flat Roof Flashing (flat roof)
ESTD.ROADJ - Adjustable Roof Flashing (1/12 to 7/12 pitch)
ESTD.ROSTP - Steep Roof Flashing (8/12 to 12/12 pitch)
Vent system components approved for use with the Estate Fireplace
are shown in Figure # 9 and Appendix A. The Estate Fireplace is also
tested and certified for use with SIMPSON DURA-VENT DIRECT
VENT GS pipe (see Optional Venting section).
NO OTHER VENTING SYSTEMS OR COMPONENTS MAY BE
USED.
Various combinations of vertical and horizontal runs may be used.
Refer to Figures # 8d, 8e, & 8g for details. For optimum performance
and flame appearance, keep the vent length to a minimum. Connec-
tions between each vent system component must be tightly joined
and sealed, and secured with sheet metal screws at each joint. A
horizontal run of vent must have a 1/4" rise for every 2 ft.of run towards
the termination.
NOTE: The minimum top exit vent
length is a combination of 16" rise
and 14" run. For longer venting
configurations, the rise and run
must be constrained to the bounda-
ries of this chart.
VERTICAL RISE
HORIZONTAL RUN
PACIFIC ENERGY
WALL TERMINATION VENTING
Fig. # 8d
NOTE: At 31 1/2" up, the maxi-
mum horizontal rear exit vent
length is 18" with a 45° elbow
(see below).
CAUTION: UNDER NO CONDITION SHOULD COMBUSTIBLE
MATERIAL BE CLOSER THAN 1 INCH FROM THE VERTICAL
AND HORIZONTAL SECTIONS OF THE PACIFIC ENERGY VENT
SYSTEM OR 1-3/4 INCHES FROM THE SIMPSON DURA-VENT
DIRECT VENT GS SYSTEM.
Exterior wall opening:
IMPORTANT: Before cutting an opening in an exterior wall, ensure
correct vent terminal location by referring to the clearance specifica-
tions noted on Figure #13.
It is preferred to cut an opening between two building framing
members to avoid any extra framing. Consult your local building
codes prior to proceeding. The vent kit will accommodate a maximum
wall thickness of 11-1/2 inches.
Having determined the vent terminal location, cut and frame an
opening of 10-1/2 inches. The opening may be round or square.
Minimum distance from the finished floor to the centre of the opening
in a flat wall is 52 inches, and 59-1/4 inches in a corner installation for
top vent, or 31 1/2" for rear vent. Height of the opening will vary with
each installation. As the horizontal vent run increases, so does the
minimum vertical rise.
NOTE: The vent must not exceed
a total length of 20 feet. Any
combination of rise and run may
be used but must be constrained
to the boundaries of this chart. For
each additional 90° elbow, reduce
vent length by 2 feet. For each
additional 45° elbow, reduce vent
length by 1 foot.
18"
1’
2’
3’
4’
5’
18"
31 1/2"