18
OUTER PIPE
INNER PIPE
SEALANT
Fig# 19f
SEALANT
Venting System Components
Dura-Vent GS Catalog #
galv.
black
6" pipe length
908B
9" pipe length
907B
12" pipe length
906
906B
24" pipe length
904
904B
36" pipe length
903
903B
48" pipe length
902
902B
11" - 14 5/8" adjustable pipe length
911B
90° elbow
990
990B
45° elbow
945
945B
High wind vertical termination cap
991
Horizontal square termination cap
984
Snorkel termination cap - 36"
981
Snorkel termination cap - 14"
982
Vinyl siding standoff
950
Round ceiling support/wall thimble
940
Cathedral ceiling support box
941
Storm collar
953
Ceiling firestop
963
Roof flashing 0/12 - 6/12
943
Roof flashing 7/12 - 12/12
943S
Wall straps
988
Wall thimble
942
Dura-Vent Pipe Adaptor
ENCD.DVADPT
Flex Pipe to Snorkel Adapter
ESTD.SNADPT
Wall Termination Venting
To connect the Dura-Vent GS venting system to the
Estate Fireplace flue outlet, a Dura-Vent Pipe Adaptor is
required.
A list of Dura-Vent system components is shown in Fig.
#19e.
Top Vent
A minimum 6" vertical length must be installed before
the first 90° elbow. With this minimum vertical rise, a
maximum horizontal run of 18" is permitted. For longer
horizontal runs, the vertical rise must also increase.
The rise and run must be constrained to the boundries
of the chart shown in figure #20a, c, d, & e.
A horizontal run of vent must have a 1/4" rise for every
2 ft.of run towards the termination.
Rear Vent
Refer to Figures #19a-d for allowable configurations.
Roof Termination Venting
To connect the Dura-Vent GS venting system to the
Estate Fireplace flue outlet, a Dura-Vent Pipe Adaptor is
required.
Top Vent
A minimum 4' vertical length must be installed before the
termination cap or the first 90° elbow. The total vent
length must not exceed 40'. Any combination of rise and
run may be used but must be constrained to the boundries
of the chart shown in figure #20b & c.
A horizontal run of vent must have a 1/4" rise for every
2 ft.of run towards the termination.
Rear Vent
Refer to Figures #19a-d for allowable configurations.
Vent Pipe Sealant
(supplied with the appliance)
SIMPSON DURA-VENT DIRECT VENT GS pipe: All
vent pipe sections must be sealed. Run a 1/8 inch wide
bead of sealant around the male end of the outer pipe
and female end of the inner pipe as shown in Figure
#19f, and twist-lock the vent pipe sections together.
Fig. # 19e