![Paccar DAF POWERCHOICE 360X Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/paccar/daf-powerchoice-360x/daf-powerchoice-360x_installation-manual_3108992021.webp)
DC-connections
5.4.4
Note:
The details of the electrical installation mentioned below are for each of the base
product cabinet.
After installation checks
5.5
1. Make sure, visually and by measurement, that the connections are made correctly
and at proper locations.
- The connections are torque tight and marked.
- The resistance is below 0.0250 mOhm per high current connection
2. Do an insulation check of the AC supply cables utilizing IEC 60364-6
or local equivalent procedure.
- The AC supply cables are fit for service and not showing significant
damage from installation.
- The insulation test report is completed and available.
3. If the test fails, do any necessary corrective work such as replacing the defective cable.
21