Last update: 30/11/2020 

  2 

DIMENSIONAL DRAWING

 

 

 

SELECTION

 

This product is to be utilized with clean fresh water, even slightly additivated with normal detergents. For use involving 
different or corrosive liquids, contact the PA Technical department. Appropriate filtration should be installed when using 
impure liquids. Choose the valve in line with the working data of the machine where to be installed (permissible pressure, 
maximum flow rate and rated temperature of the system). In any case, any over-pressure of the machine must not 
exceed the permissible pressure marked on the valve. 

 

OPERATION 

The valve limits the maximum pressure of the system. In the event of over-pressure, this relief valve will open to allow 
the liquid to by-pass. During normal system operation, a shutter driven by a spring will keep the bypass opening close. 
The set valve pressure can be regulated by adjusting the spring load by means of the dedicated adjusting screw. 

 

INSTALLATION 

This product is intended to be incorporated on a finished machine.On a machine that produces hot water,this valve must 
be fitted upstream the heat generator. In addition it is recommended to install devices that limit the fluid temperature 
accidental increase. 

 
DISCHARGE SYSTEM AND WATER ADDUCTION 

It is advisable to direct the bypass discharge liquid to a baffled tank that will reduce possible turbolence and air bubbles 
generated by the immission of the bypass flow, which could be harmful for the pump. 
When large flow volumes, close tho the max flow rate, are used, it is not advisable to return the bypass liquid to the 
pump as this may cause dangerous pressure spikes, dangerous for the pump. 

 

PRESSURE ADJUSTMENT/SETTING 

The valve is supplied without pressure setting. The setting is done with the system “on”and with pressure inside the 
circuit. The valve setting pressure is achieved by operating on the adjusting screw (pos.7): by screwing it, the set 
pressure will increase.Once the desired pressure is attained, block the screw by locking the counternut (pos.7) 
 

TROUBLESHOOTING 

PROBLEMS 

PROBABLE CAUSES 

SOLUTIONS 

Leaking out the bypass port during 

normal system operation. 

- Seat or shutter is worn. 

- Foreing material is jammed between seat  

  and shutter. 

 

- Replace. 

- Clean. 

- System working pressure is above  

   the set pressure. 

- Re-set the system  

   pressure. 

 

 
 

Содержание 60.0590.00

Страница 1: ...nfo pa etl it VS 80A 150 280 INOX 316 ATEX Technical Manual E 228 Relief valve TECHNICAL SPECIFICATIONS Construction material Body and internal parts made of stainless steel Aisi316 Rated temperature...

Страница 2: ...hot water this valve must be fitted upstream the heat generator In addition it is recommended to install devices that limit the fluid temperature accidental increase DISCHARGE SYSTEM AND WATER ADDUCT...

Страница 3: ...g see ATEX SAFETY NOTE SN03 PN 10 9408 06 SERVICING The relief valve useful life is 10 years with general inspection and service after 5 years The life duration depends from the working conditions suc...

Страница 4: ...guenteDirettivaEuropea to which this declaration refers is in conformity with the following European Directive 2014 34 UE ATEX 2014 34 EU ATEX Laconformit stataverificatainbasedeirequisitidellenormeod...

Страница 5: ...Rev 00 Date 27 10 2020 Pag 1 of 10 DOCUMENT REVISION REV DATE MODIFICATION 00 27 10 2020 First issue PREPARED BY RGQ Quality manager Michele QUATTRONE CHECKED BY DUT Technical manager Fabio PEDRONI AP...

Страница 6: ...4 1 WORKING ADJUSTMENT 6 3 4 2 SUITABLE NON SUITABLE USE 6 3 4 3 DANGEROUS AREAS 7 3 4 4 DANGER POSSIBLE RISKS 7 3 4 5 PPE PERSONAL PROTECTIVE EQUIPMENT PROCEDURES TRAINING 8 3 5 SYSTEM PROCEDURES 8...

Страница 7: ...uced using an evaluation design and manufacturing process which complies the essential safety requirements of Directive 2014 34 EU The assembler has the responsibility to verify the compliance with ot...

Страница 8: ...talled in a potentially explosive environment The appliance in question grants that potential sources of priming are not activated in normal functioning and even in case of foreseeable and rare failur...

Страница 9: ...d movement of the valves must guarantee that they are not subject to shock impacts tumbles deterioration and other damaging which could compromise the function of the valve Any eventual damage must be...

Страница 10: ...ipotential connections Inspection after installation to be carried out by the assembler or end user in particular the perfect coupling of usage at the various openings keep to the limit levels of emis...

Страница 11: ...excluded during a normal function even if they can occur in case of foreseen and rare dysfunctions they can be caused by friction knocks or abrasion hammering Ultrasounds acoustic danger Tank measurem...

Страница 12: ...ble liquids noxious substances etc Others in relation to type of use The use of the valve must foresee a precise training formation It is necessary to pertain to the application of the local safety re...

Страница 13: ...cleaning it is necessary to use non corrosive products or solutions suitable to remove the work residue and that do not damage the O ring surfaces For the cleaning operations do not use aggressive che...

Страница 14: ...f this safety note After reinstalling the device and before placing the equipment under pressure verify the correct tightness between the connections and apparatus and its efficiency 3 6 5 REPLACEMENT...

Страница 15: ...Hex nut M10 Sst 3 10 8 60 0406 31R Spring holding washer brass 1 10 9 10 3174 10R O ring 2 62x9 93 mm Vi 70 1 10 10 10 4015 00R Back up ring 10x14 5x1 2 mm 1 10 11 15 1032 00R Roll pin 3x18 mm Sst 1 1...

Отзывы: