VZR.235900.000 IG
Cube С-04 Turnstile
Installation Guidelines
30
In case of confirming the card withdrawal evidence by the internal sensors,
the card collector generates the signal for AD by means of the group of contacts Let
Go and by means of the group of contacts Card Inside for AMCS. At that, the side
display panel illuminates green light.
Free Pass-GND Group of Contacts
(signal for passage authorization without
card withdrawal)
FreePass and GND Contacts. The input, which receives the signal from
AMCS controller and authorizes passage without card withdrawal (permanent
pass).
In case of receiving the signal for passage authorization without card
withdrawal, the card collector generates the signal for AD by means of group of
contacts Let Go. At that, the side display panel illuminates green light.
The Cardcollector Free Pass Input can operate both in potential and in pulse
mode (actuation by the evidence of contact closing).
The pulse mode is set by default. At that, upon starting, the card collector
issues 1 sound signal.
For switching to the potential operating mode, it is necessary:
1)
to disconnect power supply;
2)
to wait for D11 LED on the card collector board going off;
3)
to push and hold BUT1 button on the card collector board;
4)
to switch on the power supply;
5)
to hold BUT1 button until the card collector emits 2 sound signals, which
indicate its switching to potential operating mode.
Setup of the set mode remains when switching off the power supply. To
return to the pulse mode, repeat the above sequence of operations.
Card Inside Group of Contacts
(card withdrawal confirmation signal)