VZR.235900.000 IG
Cube С-04 Turnstile
Installation Guidelines
21
ATTENTION:
IN CASE OF CLOSING ONE OF INPUTS, THE STOP-
COMMANDS FROM THE PANEL ARE NOT ACCEPTED, BECAUSE AMCS IS OF
THE HIGHER PRIORITY.
The STOP input is potential, i.e. as long as the the input is closed to
GND contact, the turnstile operates in the corresponding mode. After opening the
contacts, the turnstile switches to “Stop” mode regardless of the mode that has been
on before AMCS operation.
LEFT and RIGHT inputs can operate both in potential and pulse mode
(actuation based on the evidence of closing to GND contact). The pulse mode is
set by default.
For switching to potential mode of operation, a jumper (Figure 11 -
Х1) shall
be set to “ON” position on the mainboard. In this case, the left/right passage mode
is switched on only for the time of the control signal supply to the LEFT/RIGHT
inputs.
The free passage mode can be set by simultaneous issue of control signals
to both inputs. Priority of LEFT and RIGHT inputs during switching to the pulse
mode remains unchanged.