5.7
1) Optional external interlock switches are
required with some Sectional & Rolling Steel
Doors to prevent the door from operating
under certain conditions including the
following:
•
If the door is equipped with a function-
ing door lock, an interlock switch must be
installed to prevent electric operation when
the lock is engaged.
•
If the door is equipped with a pedestrian
pass-through door, an interlock switch (B)
must be installed at the pass-through door
in order to prevent electrical operation
when the pass-through door is open.
2) The Switches must be set in the field.
3) An OPEN circuit must be provided to pre-
vent electrical operation.
Interlock Switches
Pass
door
interlock
:
SWITCH
075412-0000
(N.O.)
Should
be
open
when
door
is
open.
Closed when
door
is
closed.
OPERATOR
HOIST
INTERLOCK
SWITCH
B
ANGLE
405964-0000
Switches must
be set in
A
SWITCH
110325.0001
(N.C.)
STANDARD
SLIDELOCK
TRACK
Side
lock
interlock:
Should
be
open
when
door
is
locked.
Closed
when
door
is
unlocked.
NOTE
: All switches must be wired in Series.
WHT/
VIO VIO
Section 5: Intrinsically Safe Wiring
NOTE: N/C Interlock switches MUST be
connected in series for proper operation.
Junction Box