Outdoor Lifestyles by Hearth & Home Technologies • Palazzo Installation Manual • 4082-311 Rev. A • 06/08/15
FP
= FIREPLACE OPENING
X
= AIR SUPP LY INLET
= AREA WHERE FIREPLACE IS NOT PERMITTED
O
N
P
R
Q
FP
(See Note 2)
D
E
L
FP
A
H
M
X
J or K
I
G
F
FP
FP
FP
FP
B
B
B
A
= 24 in. . . . . . . . . . clearances above grade,
veranda, porch, deck or
balcony.
B
= 12 in. . . . . . . . . . clearances to window or door
that may be opened, or to
permanently closed window.
20 in. . . . . . . . . . vinyl windows or siding.
D
= 50 in. . . . . . . . . . vertical clearance to unventi-
lated soffit or to ventilated soffit
located above the terminal.
60 in. . . . . . . . . . vinyl clad soffits.
F
= 9 in. . . . . . . . . . clearance to outside corner.
G* = 7 in. . . . . . . . . . clearance to inside corner,
non-vinyl siding.
H
=
3 ft. (Canada) . not to be installed above a gas
meter/regulator assembly within
3 ft (914 mm) horizontally from
the center line of the regulator.
I
=
3 ft. (USA)
6 ft. (Canada) . clearance to service regulator
vent outlet and electric service.
J
= 9 in. (USA)
12 in. (Canada) . clearance to non-mechanical air
supply inlet to building or the
combustion air inlet to any other
appliance.
K
=
3 ft. (USA)
6 ft. (Canada) . clearance to a mechanical air
supply inlet.
L
=
. . . . . . . . . . (See note 4)
M** = 50 in. . . . . . . . . . clearance under veranda, porch,
deck, balcony or overhang.
Not allowed: . . . . . . vinyl
N* = 14 in. . . . . . . . . . clearance to inside corner,
non-vinyl siding. (Alcove)
O
= 50 in.
P
= 88 in.
* 48 in. minimum for vinyl windows or vinyl siding.
** only permitted if veranda, porch, deck or balcony is fully open
on a minimum of 2 sides beneath the floor, or if the screened
porch guidelines are followed.
Note 1:
Local codes or regulations may require different clearances.
Note 2:
Appliance in an alcove space (spaces open only on one side
and with an overhang) are permitted with the dimensions
specified for vinyl or non-vinyl siding and soffits.
1)
There must
be a 3 ft minimum between terminations or between the
fireplace and termination.
2)
All mechanical air intakes within 10
ft of a termination must be a minimum of 3 ft below the fireplace
hood.
3)
All gravity air intakes within 3 ft of the fireplace opening
must be a minimum of 1 ft below the termination.
This fireplace is approved for installation onto screen porches with the
following guidelines:
Minimum porch area: 96 sq ft
Minimum ceiling height: 88 in.
Minimum of two walls must be screened
Minimum top of screen height, side walls: 80 in.
Minimum screen area: 64 sq ft
Note 3:
There may be some odor and small amounts of soot associated
with burning outdoor gas fireplaces on a screened porch. Consider
prevailing wind direction for best flame performance.
___________________________________________________________________________
___________________________________________________________________________
___________________________________________________________________________
Q
MIN
R
MAX
Palazzo
10 feet
2 x Q
ACTUAL
1 additional termination cap
Q + 3 feet 1 x Q
ACTUAL
2 additional termination caps Q + 6 feet 2/3 x Q
ACTUAL
3 additional termination caps Q + 9 feet 1/2 x Q
ACTUAL
R
MAX
= (2 / # caps plus fireplace ) x Q
ACTUAL
Alcove
Note 4:
For appliances installed facing or opening onto public property or
property servicing more than one single family dwelling, such as
driveways, sidewalks, etc. refer to local building codes/regulations for
proper clearances.
C. Vent Minimum Clearances
Figure 3.5 Minimum Clearances