Meas. A that controls relay
Meas. 1 Outdoor temperatur
Meas. 2 H1 Supply water
Meas. 3 H1 Room measurem. TMR
Meas. 4 Solar collector
Meas. 5 Accumulator temp.
Meas. 6 Not in use
Relay control according to the temperature difference:
Relay control according to the valve position::
Relay control according to the time program:
> Laiteasetukset... Pumpun kesäpysäytys
Device settings > Relay control
Relay control Accord. to temp. difference
Meas. A that controls relay Solar collector >
Meas. B that controls relay Boiler temp. >
Temp.diff. (A-B) where relay is active 50 °C >
Temp.diff. (A-B) where relay is released 30 °C >
> Laiteasetukset... Pumpun kesäpysäytys
Device settings > Relay control
Relay control Accord. to H1 valve position
Valve position where relay is active 95% >
Valve position where relay is released 90% >
> Laiteasetukset... Pumpun kesäpysäytys
Device settings > Relay control
Relay control Accord. to the time program
Meas. B that controls relay
Meas. 1 Outdoor temperatur
Meas. 2 H1 Supply water
Meas. 3 H1 Room measurem. TMR
Meas. 4 Solar collector
Meas. 5 Accumulator temp.
Meas. 6 Not in use
Here you can select which temperature differences control the relay.
Subtract temperature measurement B from temperature measure-
ment A. If the measurement channel has not been taken into use or
you want to use it for something else, make the change at “Measu-
rement channel settings” in device settings.
Temperature difference (A-B), when the relay is active (ON):
The right temperature difference between the solar collector and
boiler could be, e.g., 10 °C. When the temperature of the solar collec-
tor is, e.g., 10 °C higher than the boiler temperature, the solar energy
collector’s circulating pump is controlled on.
Temperature difference (A-B) when the relay is released (OFF):
If the relay continuously becomes active and then released, the set-
ting is too small.
Relay control is activated when the difference between two tempera-
tures is large enough. Example: Solar collector/ Boiler temperature.
Relay control is activated when the valve has opened enough.
Example: At first the water in the boiler is heated using more inex-
pensive energy (e.g., an air-to-water heat pump). When the valve is
95% open a run command is given to the oil burner. The oil burner is
turned off when the position of the valve is 90%.
The relay changes its mode according to its week/ 24 hour program.
Example: Using electric heat at night for an additional heating sour-
ce. See p. 17 to create the relay’s week/24 hour program
Temp.diff. (A-B) where relay is active tive (ON)
50
°C
min: 0 max: 95
Temp.diff. (A-B) where relay is released
30
°C
min: 0 max: 95
Valve position where relay is active
95%
min: 0 max: 100
Valve position where relay is released
90 %
min: 0 max: 50
Indication of alarm:
> Laiteasetukset... Pumpun kesäpysäytys
Device settings > Relay control
Relay control General alarm
Oh
The relay is always activated when the EH-800 controller has an
alarm that has not been acknowledged (see p. 17).