Home/Away control (H/A)
When a home control command is received, the controller by-passes the present temperatu-
re drop command in use and switches to nominal temperature.
An away control command causes the controller to switch to temperature drop. The control-
ler switches to a big temperature drop if the week program or exception calendar controls it
to a big temperature drop.
In the no Home/Away control mode the controller is on automatic control and follows the
week program and exception calendar. If time programs have not been made, the controller
is in the nominal temperature mode.
Home
Away
No H/A control
Home/Away control
Explanation
The “Home” and “Away” controls can only be used if the controller is on automatic control.
The control command can be given from the controller’s menu, from the home/away switch
connected to the controller or from a mobile phone. Regardless of from where the control
command comes, the controller’s Home/Away display is updated. The last control command
is in use. The control command affects both H1 and H2 control circuits.
Key words:
Home
Away
The Home/Away control is only in effect if the controller is on automatic control.
When you send a Home or Away message, the controller sends back an OUMAN mes-
sage showing that the HOME or AWAY control is on.
Muut ohjaukset -> Home/Away control
Example 1. The controller does not have a week program or exception calendar program:
An “Away”
command causes the controller to switch to a temperature drop.
A “Home”
command causes the controller to switch back to a nominal temperature mode.
Example 2. The controller has a week program:
An “Away”
command causes the controller to switch from the weekly program to a temperature drop.
A “Home”
command causes the controller to switch to a nominal temperature mode and then begin temperature drops
according to the weekly calendar.
Example 3. The temperature drop has been made with the exception calendar and you want to temporarily switch to a nominal
temperature.
A “Home”
control causes the controller to switch to the nominal temperature mode.
An “Away”
control command causes the controller to switch back to a temperature level controlled by the exception calendar.
Home/Away control
Home
No H/A control
Away