Installation
________________________________________________________________________________
page 4
OSRAM operating instructions DALI Repeater LI
2. Repeater in Touch DIM operation for up to 64 ECG:
L
N
PE
DA
DA
3. Repeater in Touch DIM operation for up to 64 x 64 EVG:
Hints:
•
In Touch DIM operation the DALI input terminals must not be connected.
•
The maximal overall wire length at the push button input should not exceed 100 m. Further points
of control can be achieved by parallel connection of several push buttons. Push buttons with glow
indication lamps in parallel to the push to make contact are inapplicable.
•
Both outputs of the DALI Repeater LI are electrically interconnected. To simplify the connection the
layout is done by pairs.
•
In total over both outputs a maximum number of 64 DALI ECG or DALI REPEATERS may be
connected.