Operation
________________________________________________________________________________
OSRAM operating instructions DALI Repeater LI
page 5
DALI operation with supervisory control unit
Before starting up the DALI control unit the DALI Repeater should be initialised as follows:
•
Initialise is started by pressing the integrated “service” button of the DALI REPEATER LI for at
least 0.5 s.
•
During initialise process the highest minimal dimming level of the connected DALI devices is
detected and stored. During this process the LED will flash in yellow.
The DALI REPEATER LI supports all addressing and commissioning methods offered by the DALI
standard. Independently from the connected device types at the output, the Repeater will identify
itself and detected by the control unit as ballast for fluorescent lamps.
If the address assignment is done by the “PHSICAL SELECTION” method, please press the service
button or cause a lamp fail at one of the connected ballasts when the procedure of the control unit
requires that.
Hints to the DALI operation:
•
All devices connected to the outputs will always act synchronous in broadcast mode. No
addresses are assigned at the output side.
•
Please follow the instructions of the control unit connected to DALI input of the Repeater.
Please see also "Indication LED" and "Service button".
Touch DIM operation
Before first manual operation the DALI Repeater should be initialised as follows:
•
Initialise is started by pressing the integrated “service” button of the DALI REPEATER LI for at
least 0.5 s.
•
During initialise process the highest minimal dimming level of the connected DALI devices is
detected and stored. During this process the LED will flash in yellow.
After that, please
perform a long push
(> 0,5 0s) to one of the connected push to make buttons. The
DALI REPEATER LI will be switched over from DALI to
Touch DIM
operation by this.
Touch DIM-operation in brief:
•
Switch on/off :
Short press to the connected push button (< 0,5 s)
•
Dimming:
Long press (> 0,5 s)
(Dimming direction will change with every long press)
•
Store memory value:
Double click: 2 short presses within 0,4 s when the lamps
are
switched on.
•
Delete memory value:
Double click: 2 short presses within 0,4 s when the lamps
are
switched off.
Hints to the Touch DIM operation:
•
When the lamps are switched off a long press will cause that the lamps are switched on and
dimmed up until the button is released ort he maximum brigthness is reached.
•
If the maximal or minimal brightness is reached the dimming process is stopped. A change of
dimming direction will be performed not before the button is released and pressed again.
•
If the memory value is deleted, the last dimming level before switch off is recalled when the
lamps are switched on by a short press.
Please see also "Indication LED" and "Service button".