16
Installation
4.1
Installation conditions
Installation position
Terminals on top and bottom
Horizontal spacing
On both sides 18 mm
Minimum vertical rail grid spacing
115 mm (90 + 25 mm)
(excluding conduit)
Recommended vertical rail grid spacing
160 mm (with 40 mm conduit)
4.2
Mounting process
1
2
The SYMPL pro Node (e:pix) / SYMPL essential Node is designed to mount
onto a 35mm DIN rail (EN 60715) in a vertical position.
1. Clip the device to the rail from
top.
2. Apply gentle pressure to the
top front to snap it in place. The
device has been mounted
successfully.
You can also mount the device on any flat surface. Use a 3 to 3.5mm screw
for the hanger hole.
For mechanical stability, mounting on a rail is recommended.
4.3
Ethernet connection
The pin-assignment of the Ethernet port corresponds to RJ45 standards.
You can use every common Ethernet component, like cable, splitters, and
switches. Connect the SYMPL pro Node (e:pix) / SYMPL essential Node at
the designated Ethernet interface with a patch cable (RJ45, CAT5).
!
Ground the Ethernet cable for outdoor installations (optional
for indoor only).
Содержание AM255360031
Страница 7: ...07 English...
Страница 30: ...30 Deutsch...
Страница 55: ...55 Zertifizierung Dimensions Abmessungen All dimensions in mm Alle Abmessungen in mm 62 92 143...