Safety and Servicing

Maintenance must be carried out by a competent person.

7.1 Safety Cut-out

The safety cut-out operates if:

1. Wiring is incorrect.

2. The immersion heater thermostat or cylinder thermostat fails.

3. Thermostat is set too high.

4. Remember before resetting the safety cut-out or altering the thermostat setting, isolate electrical supply to the unit prior

to removal of the electrical box lid.

5. Reduce thermostat setting and press the reset button. After adjustments are completed, ensure the lid to the electrical

box is replaced.

6. If still out of operation, contact installer.

7.2 Intermittent or slow discharge from tundish

1. Turn off the electrical supply to the immersion heaters.

2. Turn off cold water supply valve.

3. Open a hot tap.

4. Turn the knob on the Temperature and  Pressure Relief Valve (5) to the left and hold in this position for thirty seconds.

5. Attach a foot pump with a schraeder (car type) valve to the expansion vessel.

6. Pump up to 3 bar

7. Open cold water supply valve.

8. When water flows through open tap, close tap

9. Turn on electrical supply to the immersion heaters.

7.3  Continuous very hot water discharge from tundish 

This indicates a malfunction of a thermal cut-out, operating thermostat or the combined temperature and pressure relief 

valve. Turn off the electrical supply to the immersion heater and also isolate an indirect unit from the 

Heat Pump

. Contact the 

installer or competent engineer.

7.4  Expansion vessel maintenance

The expansion vessels do not require annual maintenance and should not be tampered with unless an intermittent or slow 

discharge from the tundish occurs when water is being heated. In this situation, maintenance must be carried out by 

competent person and the precharge pressure must be restored to the original value. An annual visual inspection is 

recommended. Important: To check the precharge the expansion vessel must be completely empty of water. If the precharge 

pressure is different from the value shown on the label it must be restored to the original value. 

Do not remove expansion vessel without depressurising the cylinder and draining 10 litres of water from the drain valve at 

the base of the cylinder.

7.5 Guarantee

Cylinder should be serviced annually and the log book should be updated in order to validate guarantee. The log book and 

service records act as guarantee document. For terms of guarantee please see the log book on page 1

5.

7.6 Servicing Procedure:
7.6.1 Expansion relief valve

Ensure that expansion relief valve works by manually opening to discharge water to tundish.

7.6.2 Pressure reducing valve

Isolate the cold water supply and open a ground floor cold tap. Unscrew the pressure reducing cartridge. Clean the filter 

mesh and the cartridge under running water. Replace cartridge ensuring that strainer is correctly located and reassemble the 

unit. 

7.6.3 Expansion relief cartridge

Isolate the cold supply and open a ground floor cold tap. unscrew blue expansion  relief headwork from valve body. Clean 

valve seat face and seating - do not scratch or damage either seat face or seating. Refit in reverse order. Do not overtighten.

7.6.4  Temperature and Pressure relief valve

Ensure that Temperature & Pressure Relief valve works by manually opening to discharge water to tundish.

7.6.5 Internal inspection

The immersion heater can be removed to provide visual inspection access to the cylinder. 

Содержание DGC 200

Страница 1: ...in hot water cylinders in accordance with Building Regulation Part L Domestic Heating Compliance Guide This OSO cylinder must be installed by a competent person and be installed in compliance with the...

Страница 2: ...cludes pressure reducing valve line strainer balanced cold water take off for shower or bidet only check and expansion valve Tundish 3 4 x 22mm Elbow Drain Cock Motorised valve Expansion vessel 1 4 Co...

Страница 3: ...Control Thermostat 80345 10 Cold Feed Tube Not supplied see Table 1 11 Hot Water Outlet 3 4 BSP 12 Elbow Drain Cock 250445 13 Discharge Pipe Not supplied 14 Motorised Valve Not Factory Fitted 15 Expan...

Страница 4: ...6 above 3 1 8 Connect 15mm copper tube from the expansion relief valve 4 and also from the T P valve 5 and join together in a Tee as shown on page 3 3 1 9 Fit the tundish 6 to the bottom connection of...

Страница 5: ...ture and pressure relief valve An internal 18 mm hose can be applied to lead the water to a gully sink or similar 5 2 System flushing This will not be necessary under normal circumstances as the line...

Страница 6: ...cylinder thermostat set at 60 C in line with current government guidelines Lowering the temperature will substantially reduce the amount of usable hot water available on a daily basis and could resul...

Страница 7: ...follow upper diagram Wiring for Standard Heat Pump Thermistor controlled Heat Pumps Many popular Heat Pumps now use a thermistor principle A thermistor temperature sensor is supplied with the Heat Pu...

Страница 8: ...e of cylinder 1 2 E 2 3 1 T6360B 3 3 1 4 G O B1 Br G Y N L E N L E N L ST6400 Heat pump Pump 1 2 3 3 2 3 2 2 2 3 1 V4043H Room thermostat Zone Valve DHW supplied Isolated Mains Supply From Fused Spur...

Страница 9: ...harge from the tundish occurs when water is being heated In this situation maintenance must be carried out by competent person and the precharge pressure must be restored to the original value An annu...

Страница 10: ...tions to motorised valve see 3 6 on page 5 and wiring diagrams on page7 and 8 Intermittent water discharge 1 Reduced expansion vessel charge 1 Follow instruction page 9 Intermittent or slow water disc...

Страница 11: ......

Страница 12: ...lve 6 0 Bar 214005 Part no PRE355030 355030 550853 REDC355030 250445 71242 92000 80345 80314 AX18 AX24 Description Expansion Relief Cartridge Expansion relief valve 8 bar Multibloc Temperature pressur...

Страница 13: ...Regulations 3 Failure to install and commission this appliance to the manufacturer s instructions may invalidate the guarantee The above does not affect your statutory rights For full details on the H...

Страница 14: ...rdance with European Council Directive 98 83 EC or revised version at the date of installation and is not fed with water from a private supply Particular Chloride content Max 250 mg l Sulphate content...

Страница 15: ...ISCHARGE TESTED IS PRIMARY ENERGY SOURCE CUT OUT FITTED NORMALLY 2 PORT VALVE WHAT IS THE PRESSURE REDUCING VALVE SETTING IF FITTED WHERE IS OPERATING PRESSURE REDUCING VALVE SITUATED NO YES NO YES NO...

Страница 16: ...ENTS SIGNATURE DATE ENGINEER NAME SERVICE 5 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 7 COMPANY NAME TEL No COMMENTS SIGNATURE DATE ENGINEER NAME SERVICE 9 COMPANY NAME TEL No...

Отзывы: