7
2.Automatic mode in power use
13:00
– 14:00: The outdoor temperature is in the TIME1-TIME2 range (default 5-15 ° C), and the
fresh air runs for 1 hour;
13:00
– 15:00: The outdoor temperature is in the TIME2-TIME3 range (default 15-23 ° C), and the
fresh air runs for 2h;
13:00
– 16:00: The outdoor temperature is in the TIME3-TIME4 range (default 23 ° C -28 ° C), and
the fresh air runs for 3h.
By adjusting the temperature values represented by TIME1, 2, 3, and 4, the start-stop temperature
and ventilation time of the fresh air can be adjusted. For example, lowering TIME2 and TIME3 can
extend the ventilation time; conversely, increasing TIME2 and TIME3 can reduce the ventilation
time.
3.Humidity control mode in solar