5
Electricity
LCD Thermostat
All models can only introduce fresh outdoor air to regulate indoor
temperature and humidity.
Automatic mode
In the Spring/Fall/Winter
In the Summer
Automatic ventilation
When outdoor temperature is
higher than indoor.
When outdoor temperature is lower
than indoor.
Ventilation 1-3h from
13pm, keep the room
fresh.
Outdoor 5-15
℃
(adjustable)
Outdoor 15-23
℃
(adjustable)
Outdoor 23-28
℃
(adjustable)
Ventilate for 1h
2 hours
3 hours
Outdoor air (moisture content) is dryer than indoor
and indoor relative humidity
≥85%
Outdoor air (moisture content) is wetter than indoor
and indoor relative humidity
≤35%
Will ventilate to regulate moisture content indoor
In the process of ventilation, if the following conditions occur, the fan stops working.
Outdoor air (moisture content) is dryer than indoor
and indoor relative humidity
≤35%
Outdoor air (moisture content) is wetter than indoor
and indoor relative humidity
≥85%
Humidity control mode
:
Indoor relative humidity adjustment range: 30% -45%; 60% -75%.
Outdoor air (moisture content) is dryer than indoor
and indoor relative humidity
≥70%
Outdoor air (moisture content) is wetter than indoor
and indoor relative humidity
≤40%
Will ventilate to regulate moisture content indoor
Manual mode
Can set 2 time periods freely to ventilation.
Heating fresh air mode
In the Spring/Fall/Winter
In the Summer
Automatic ventilation
When outdoor temperature is
higher than indoor.
When outdoor temperature is lower
than indoor.
Ventilation 1-3h from
13pm, keep the room
fresh.
Outdoor 5-15
℃
(adjustable)
Outdoor 15-23
℃
(adjustable)
Outdoor 23-28
℃
(adjustable)
Ventilate for 1h
2 hours
3 hours
Operation
⚫
During the operation, some icons or parameters will flash, indicating that they are being
adjusted. If they are not operated within 10 seconds, the display will be on for a long time,
indicating that they are in the state of the icon or parameter. If there is no operation for 10
minutes, the screen will turn off.
⚫
The temperature and humidity display, or the operation of the fan and automatic air vent will
have some lag. The program will run automatically.
⚫
Pressing the SET button a third time displays the preset room temperature in this mode, which