18
General Clearances
Viewing Area Clearances
The viewing area clearance zone is an area that extends perpendicular from the fireplace viewing area. The depth of the viewing
area clearance zone depends on the combustibility of the material in question. Distance is measured from the fireplace heat barrier.
Non-Combustible Materials
Must be minimum
12 inches
from fireplace viewing area.
Combustible Materials
Must
be
minimum
36 inches
from fireplace viewing area.
Materials (including combustible flooring and combustible finish material) are permitted below and around the viewing area clearance
zone.
IMPORTANT NOTE: When placing material near the glass, take care to consider fireplace serviceability. It is strongly
recommended that any items/materials placed in front of the front (long) glass be movable for easy access to the fireplace
during servicing. Recommendation does not apply to side (short) glass(es).
Viewing Area Clearances Per Model
Front
Tunnel
Corner: Left Side
Corner: Ride Side
Space Creator
Three Sided