IG-175-EN version 02; 17/06/2016
21
General Instructions
ekor.gid
Main components of ekor.gid
3.6. Other Components
There is another series of components that are external to
the ekor.gid unit and are associated with it.
3.6.1. Low Voltage Sensors
The Low Voltage Sensors are housed in the fuse holders of
the Low Voltage board and almost completely cover the
fuses.
These sensors are responsible for carrying out the meterings
required for the Advanced Monitoring of the Low Voltage
network.
The main characteristics of these Low Voltage sensors are
the following:
1. The installation of the sensors can be carried out on the
existing Low Voltage network (they can be installed on
the standard fuses).
2. The sensors do not require wired connections for each
outgoing line because they have wireless radio links
(free frequency of 433 MHz).
3. The sensors are self-powered.
4. Allows the possibility of only installing sensors on the
most interesting Low Voltage lines and over which you
want to implement the Advanced Monitoring.
5. The Low Voltage Monitor(s) that is used to carry out the
Advanced Monitoring functions is independent of the
number of Low Voltage lines to be monitored (up to 36
sensors).
Figure 3.4.
Fuse with Low Voltage sensor