IG-123-EN version 11; 23/07/2021
33
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Installation
Continuation
Cubicle
model
Manu-
facturer
Connector Connector
series
Nº
terminals
Terminal
configuration
Max. rated
current
connector
[A]
Total
connector
length
[mm]
Max. diameter
on insulation
admitted by
the connector
[mm]
cpg
.0-v/s
24-36 kV
25 kA-31.5 kA
2000-2500 A
2 connection
bushings
Nexans
EUROMOLD
Screened
400TB
2 cables
400TB + CUP
800
255
37.5
400TB + CUP
800
255
37.5
3 cables
400TB + M440CP
+ 400TB + CUP
800
500
37.5
400TB + CUP
800
255
37.5
4 cables
400TB + M440CP
+ 400TB + CUP
800
500
37.5
400TB + M440CP
+ 400TB + CUP
800
500
37.5
2 SA
400TB + 400PB-10SA
+ CUP
800
410
37.5
400TB + CUP
800
255
37.5
3 SA
400TB + M440CP
+ 400TB + CUP
800
500
37.5
400TB + 400PB-10SA
+ CUP
800
410
37.5
440TB
2 cables
440TB + CUP
1250
255
56
440TB + CUP
1250
255
56
3 cables
440TB + M440CP
+ 440TB + CUP
1250
500
56
440TB + CUP
1250
255
56
4 cables
440TB + M440CP
+ 440TB + CUP
1250
500
56
440TB + M440CP
+ 440TB + CUP
1250
500
56
2 SA
440TB + 400PB-10SA
+ CUP
1250
410
56
440TB + CUP
1250
255
56
3 SA
440TB + M440CP
+ 440TB + CUP
1250
500
56
440TB + 400PB-10SA
+ CUP
1250
410
56
Continued on next page
Содержание velatia cpg.0