IG-123-EN version 11; 23/07/2021
51
General instructions
cpg
.0: GIS medium-voltage switchgear,
gas insulated, up to 40.5 kV,
in accordance with IEC Standard
Operations sequence
The driving mechanism is manual and drives a two-position
disconnector housed inside the gas tank. The mechanism
has two positions: closed and opened (or earthed).
Use the following operations sequence to disconnect the
voltage transformer disconnector:
1.
Move the locking lever down as far as it will go to
release the mechanism.
Figure 7.35.
Actuator mechanism locking in
cpg
.0-v
36 kV/1250 A/25 kA
Figure 7.36.
Actuator mechanism locking in
cpg
.0-v
12 kV/2000 A/25 kA
2.
Pull the handle back firmly to move the disconnector to
"opened" (or earthed) position.
Figure 7.37.
Disconnector displaced to "opened" position
cpg
.0-v
36
kV/1250 A/25 kA
Figure 7.38.
Disconnector displaced to "opened" position
cpg
.0-v
12
kV/2000 A/25 kA
Содержание velatia cpg.0