IG-150-EN version 04; 03/10/16
137
General instructions
ekor.rps
Other functions
8.7. Temperature supervision
This function checks that the unit temperature d is within
the set margin. It generates two signals:
1. Temperature higher than the maximum threshold. If
the temperature exceeds the set maximum threshold.
2. Temperature lower than the minimum threshold. If the
temperature is lower than the set maximum threshold.
The settings for this function son:
Setting
Min
Max
Step
Remarks
Enable
YES/NO
Minimum threshold [º]
- 40
0
1
Maximum threshold [º]
50
100
1
Table 8.5.
Setting
8.8. Test mode
To carry out this test, the PROCOME signals and commands
simulator program needs to be executed. When this
program is run, the text “test mode” appears on the 2nd line
of the display. This program allows to simulate PROCOME
digital signals, commands, measurements and counters.
Digital signals: At the start of the test mode the signals
sent to remote control and simulator are the real ones. This
program allows to change the values of the digital signals.
In Test Mode only the signals fictitious changes, and not
the real ones, are sent to remote control. When exiting the
test mode, the equipment sends all changes from the latest
state of the fictitious and the reals signals to remote control.
Commands: In test mode, the remote control commands
are not executed. They are sent to the simulator program
instead, which has to recognise them.
Measurements and counters: In test mode, the latest real
measurements and counters are sent to remote control
and simulator. This value is frozen and can only be changed
from the simulator program. When exiting the test mode,
the equipment sends the real measurements and counters
to remote control.
When exiting the simulator program, the equipment exits
the test mode and then the unit reference is displayed
.