PT-Link II N2-3
®
Technical Guide
PT-Link II N2-3 Interface
42
Appendix E - VCM N2 Parameters
VcmOnBoardRelaysBits
::= BIT STRING {
OnBoardRelay1
(0),
OnBoardRelay2
(1),
OnBoardRelay3
(2),
OnBoardRelay4
(3),
OnBoardRelay5
(4)
}
VcmExternal Relays1-2Bits
::= BIT STRING {
ExpansionBoard1Relay1
(0),
ExpansionBoard1Relay2
(1),
ExpansionBoard1Relay3
(2),
ExpansionBoard1Relay4
(3),
ExpansionBoard2Relay1
(4),
ExpansionBoard2Relay2
(5),
ExpansionBoard2Relay3
(6),
ExpansionBoard2Relay4
(7)
}
VcmExternal Relays2-4Bits
::= BIT STRING {
ExpansionBoard3Relay1
(0),
ExpansionBoard3Relay2
(1),
ExpansionBoard3Relay3
(2),
ExpansionBoard3Relay4
(3),
ExpansionBoard4Relay1 (4),
ExpansionBoard4Relay2
(5),
ExpansionBoard4Relay3
(6),
ExpansionBoard4Relay4
(7)
}
VcmAlarmStatusBits
::= BIT STRING {
Alarm
Group1
(0),
Alarm
Group2
(1),
Alarm
Group3
(2)
}
VcmAlarmGroup1Bits
::= BIT STRING {
SupplyTempSensorFailure
(0),
LostOutdoorTempSensorSignal
(1),
LostSpaceTempSensorSignal
(2)
}
VcmAlarmGroup2Bits
::= BIT STRING {
MechanicalCoolingAlarm
(0),
MechanicalHeatingAlarm
(1),
FanProvingAlarm
(2),
DirtyFilterDetected
(3),
SmokeDetected (4)
}
VcmAlarmGroup3Bits
::= BIT STRING {
LowSupplyAirTempAlarm
(0),
HighSupplyAirTempAlarm
(1),
LowControlTempAlarm
(2),
HighControlTempAlarm
(3)
}