PT-Link II N2-3
®
Technical Guide
PT-Link II N2-3 Interface
10
3.) Refer to the
File Transfer Window
below (
Figure 10
). In the
Con-
fi guration Tab
, under Retrieve,
click
the confi g.csv fi le in order to save
it to a destination and then open it.
Figure 10: File Transfer - Confi guration Tab
Changing the Confi g.csv File
4.) Open the confi g.csv fi le in Notepad. See
Figure 11
.
WARNING:
Only edit the confi g.csv fi le using Notepad.
DO
NOT
use Excel. Using Excel to edit the confi g.csv fi le will
corrupt its contents!
Figure 11: Confi g.csv File
5.)
Another change you may need to make is the Node_ID under ‘Client
Side Nodes’ which is the N2-3 Device Instance Number (
Figure 12)
The default is 1.You can obtain the Node ID from your BAS Integrator.
Figure 12: Client Node ID
6.)
Once all changes have been made to the text fi le, while still in
Notepad,
click
<File>
in the upper left and then
click
<Save>
. Now
close the fi le and return
to the
FS-GUI Screen
open in your browser.
NOTE:
Do not rename the fi le. The fi le must always be named
“
confi g.csv
”; otherwise, it will be ignored by the PT-
Link.
7.) In the
File Transfer Window
under Update Confi guration,
click
<Choose Files>
or
<Browse>
and locate the confi g.csv fi le you just
saved. Then
click
<Submit>
. See
Figure 13
.
Wait until the message,
“Confi guration update complete” appears and then
click
the
<System
Restart>
button at the bottom of the
File Transfer Window
to activate
the new confi guration fi le.
Figure 13: Update Confi guration