background image

 PT-Link II N2-3

®

 Technical Guide

PT-Link II N2-3 Interface 

38

Appendix E - VCM N2 Parameters

N2 Parameters for the VCM Controller

Parameter

Name

Object

Description

Limits

Bypass 

Damper
Position

ByPasDmp

AI: 153

Current position of 

the bypass damper 

signal.

Return 

Damper
Position

RaDmp

AI: 154

Current position of 

the return damper 

signal.

Outdoor Air 

Dew Point

OaDwpt

AI: 47

Current

calculated outdoor 

air dewpoint added 

on version 1.09.

Current 

Supply Air 

Setpoint

SaTpStM

AI: 82

SAT/Reset Current 

SAT Cooling or 

Heating setpoint 

if there is no reset 

source; Current 

calculated SAT 

setpoint with Reset 

Source.

Coil

Temperature

CoilTp

AI: 181

Current coil
temperature 

reading added on 

version 1.09.

Preheater 

Setpoint

PreHtSp

AO: 196

Low Outside Air 

Ambient Protection 

Setpoint

0

100

CO

2

Setpoint

CO2St

AO: 149

When the CO

2

 

level rises above 

the CO

2

 Protection 

Limit Max Level, 

the Economizer’s 

Minimum Position 

will begin to reset 

open proportionally 

between the CO

Protection Limit 

Max LevelSetpoint 

and the Reset 

Range Setpoint.

0

3000

Static

Pressure 
Setpoint

DuctPrSt

AO: 152

This is the target 

duct pressure to be 

maintained by the 

VFD blower signal.

0.01

3

Minimum 

Outside Air 

Setpoint

MinEcoSt

AO: 151

This is the

minimum position 

of the economizer 

in the occupied 

modes.

1

100

Occupied 

Mode 

Enable 

Cooling 

Setpoint

OcpClSt

AO: 42

If the control 

temperature rises 

one degree above 

this setpoint, 

the control will 

activate the cooling 

demand. If the 

control temperature 

is the Supply Air 

Sensor, then the 

cooling demand is 

always active.

0

99

N2 Parameters for the VCM Controller

Parameter

Name

Object

Description

Limits

Occupied 

Mode 

Enable 

Heating

Setpoint

OcpHtSt

AO: 43

If the control tem-

perature drops one 

degree below

this setpoint, 

the control will 

activate the heating 

demand. If the

control temperature

is the Supply 

Air Sensor, then 

there is no heating 

demand.

0

99

Outdoor 

Air Sensor 

Offset

OaTpOst

AO: 53

If the Outdoor

Temperature 

Sensor is reading 

incorrectly, you can 

use this option to

enter an offset

temperature to 

adjust the Sensor’s 

Temperature.

-100

100

Relief

Pressure 
Setpoint

RfPrSt

AO: 118

This is the target 

building pressure 

to be maintained 

by the VFD Relief 

signal.

-0.2

0.2

Return 

Air Sensor 

Offset

RaTpOst

AO: 65

If the Return 

Temperature 

Sensor is reading 

incorrectly, you 

can use this option 

to enter an offset 

temperature to 

adjust the Sensor’s 

Temperature.

-100

100

Schedule 

Force

SchdFrc

AO: 66

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor 

Offset

SpcTpOst

AO: 71

If the Space

Temperature

Sensor is reading

incorrectly, you can 

use this option to 

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT/Reset 

Source 

Cooling 

Setpoint

SaClSt

AO: 77

Supply Air setpoint 

or Reset Source 

target temperature 

in Cooling Mode.

40

80

SAT/Reset 

Source 

Heating

Setpoint

SaHtSt

AO: 78

Supply Air setpoint 

or Reset Source 

target temperature 

in Heating Mode.

40

200

Содержание PT-Link II N2-3

Страница 1: ...roller Code Y200921 VCM Controller Code SS1016 Y200409 Y200616 Y200822 www orioncontrols com WattMaster Label LB102080 01 Rev 01A OE368 23N N2 3 PT LINK II PROTOCOL TRANSLATOR FOR N2 24 VAC GND LOOP L...

Страница 2: ...nfiguring the PT Link II Controller 6 PT Link II Hardware Connection 6 Computer IP Address Set up for Windows NT XP 7 Computer IP Address Set up for Windows Vista 7 or 8 8 Connecting to the PT Link II...

Страница 3: ...gateway to N2 devices as if the values were originating from N2 objects Allows N2 devices to modify point values on the Orion controller side of the PT Link II N2 by using standard N2 write services...

Страница 4: ...g steps will get you up and running in no time 1 Familiarize yourself with the PT Link II components Figure 1 NOTE The DIP Switches should be left in their default positon which is all OFF They are no...

Страница 5: ...VAC 8 VA Line Voltage Controller Controller Controller Controller 24 VAC 8 VA Line Voltage 24 VAC 8 VA SHLD T R Typical Terminal Blocks All Wiring To Be T To T SHLD G To SHLD G R To R G Wiring Notes 1...

Страница 6: ...the RUN LED is blinking continuously on the ProtoCessor Board See Figure 17 page 14 for a diagram showing the location of the ProtoCessor RUN LED Ethernet Crossover Cable Connect Ethernet Crossover Ca...

Страница 7: ...w will appear Figure 4 NOTE If any wireless connections are listed disable them by right clicking the connection and selecting Disable 3 In the Network Connections Window double click the Local Area C...

Страница 8: ...and then click Control Panel Windows 8 2 Click on the Network and Internet icon 3 Click Network and Sharing Center 4 From the shaded box in the left side of the window select Manage Network Connection...

Страница 9: ...on port 80 NOTE Computer and network firewalls must be opened for Port 80 to allow the FS GUI to function Software Requirements Mozilla Firefox 13 0 and up Microsoft Internet Explorer 8 9 Google Chrom...

Страница 10: ...Device Instance Number Figure 12 The default is 1 You can obtain the Node ID from your BAS Integrator Figure 12 Client Node ID 6 Once all changes have been made to the text file while still in Notepad...

Страница 11: ...be made in the Firmware Tab General Other Files Other files that can be updated include the FS GUI image and other files described in driver manuals The procedure for updating these is the same as for...

Страница 12: ...mula Virtual DeviceAddress unit address address set using DIPswitches on WattMaster controls Node_ID value in the PT Link II N2 configuration file 1 Example 1 The PT Link II N2 has a Node_ID equal to...

Страница 13: ...rs on the loop connected to the PT Link LED 1 will blink 4 times If the amount of blinks does not match the number of controllers connected to the loop it indicates there is a communications problem T...

Страница 14: ...is being established with the desired protocol network If both LEDs are blinking then communication is working properly If not check the protocol network wiring and the baud rate in the configuration...

Страница 15: ...the PT Link II Unzip the file to the directory where you saved your PT Link II software 4 Plug the USB cable into the computer s and PT Link II s USB ports 5 A message will pop up from the lower menu...

Страница 16: ...PT Link II once again and within 5 seconds click on the Program HEX button shown above If suc cessful you should see the Progress Application HEX bar showing the progress percentage 16 When the bar sh...

Страница 17: ...Panel 3 Double click the System Icon 4 Click the Hardware tab 5 Click the Device Manager button 6 Click on the plus sign next to Ports to see all of the common ports 7 Locate the USB Serial Port COM...

Страница 18: ...that you know you are not currently using 6 Once you select the correct COM port number click OK and close any windows opened in the process of changing the port number Make note of this number becaus...

Страница 19: ...HtSp 100 OaCFM EtCFM SaCFM OACfmSt OACfmRs OACfmStM MdCmp2 HdPr1 HdPr2 CdFan1 110 CdFan2 WaterTpA WaterTpB A1LSPAlm A1LktAlm A2LSPAlm A2LktAlm B1LSPAlm B1LktAlm B2LSPAlm 120 B2LktAlm LWT1Alm LWT2Alm P...

Страница 20: ...ExRly2 ExRly3 ExRly4 ExRly5 ExRly6 80 ExRly7 ExRly8 ExRly9 ExRly10 ExRly11 ExRly12 ExRly13 ExRly14 ExRly15 ExRly16 90 CO2St MinEcoSt CO2Level ByPasDmp RaDmp RfPr OaDwpt CoilTp SaTpStM PreHtSp 100 OaC...

Страница 21: ...s 30 VfdExPos AlmSts AlmGrp1 AlmGrp2 AlmGrp3 SaTpAlm OaTpAlm SpcTpAlm MchClAlm MchHtAlm 40 PofAlm DrtFlAlm SmokeAlm LoSaAlm HiSaAlm CtrlTpCF CtrlTpHF CtrlTp InRh InRhStM 50 DptStM MdClPos MdHtPos MdHt...

Страница 22: ...setpoints by typing the new value and pressing ENTER Note that if values are being written into the array by a driver then any modifications made by grid editing will be overridden Nodes On the Nodes...

Страница 23: ...twork The FieldServer s built in DHCP server can be enabled to establish easy connection for Support purposes Set the laptop or computer to automatically obtain an IP address to use this feature Note...

Страница 24: ...place the FS GUI will return to the main screen Figure 28 Changing the User Password NOTE To disable password protection clear the Admin pass word by simply selecting Admin as the Account Name typing...

Страница 25: ...tion Pressure Cooling Heat ing Setpoint Compressor A2 Lockout Alarm A2LktAlm BI 225 Alarm that indicates Compressor A2 is locked out Compressor B1 Low Suction Pressure Alarm B1LSPAlm BI 226 Alarm that...

Страница 26: ...t Description Limits Compressor B Low Suction Pressure Alarm B1LSPAlm BI 226 Alarm that indicates Suction Pressure for Circuit B is below the Low Suction Pressure Cool ing Heating Setpoint Compressor...

Страница 27: ...urrent value of the return temperature sensor Indoor Humidity InRh AI 67 Current value of the indoor humidity sensor Space Temperature SpcTp AI 72 Current value of the space temperature sensor Current...

Страница 28: ...If the control tem perature rises one degree above this setpoint the control will activate the cooling demand If the control temperature is the Supply Air Sensor then the cooling demand is always act...

Страница 29: ...user adjustable amount If you do not want Cooling to operate during the Unoccupied Mode use the default setting of 30 F for these setpoints 0 30 N2 Properties for the VCM X Controller Parameter Name...

Страница 30: ...function has been configured REHEAT II Connected Rt2Ins BI 58 Status that indicates the MHGRV controllers is connected to the system N2 Properties for the VCM X Controller Parameter Name Object Descr...

Страница 31: ...relay 14 Expansion Relay 10 ExRly10 BI 142 Current status of relay 15 Expansion Relay 11 ExRly11 BI 143 Current status of relay 16 Expansion Relay 12 ExRly12 BI 144 Current status of relay 17 Expansi...

Страница 32: ...hSupplyAirTempAlarm 1 LowControlTempAlarm 2 HighControlTempAlarm 3 VcmxExternal Relays1 2Bits BIT STRING ExpansionBoard1Relay1 0 ExpansionBoard1Relay2 1 ExpansionBoard1Relay3 2 ExpansionBoard1Relay4 3...

Страница 33: ...88 Current position of the VFD blower fan signal Application Software Version AppVer AI 99 Current version of the software in the unit Coil Temperature Setpoint CoilTpSt AI 107 Current Coil Temperatur...

Страница 34: ...Unoccupied Mode 1 Forced On 2 Forced Off 0 2 Space Sensor Offset SpcTpOst AO 71 If the Space Temperature Sensor is reading incorrectly you can use this option to enter an offset temperature to adjust...

Страница 35: ...pAlm BI 2 Alarm that indicates a failure in the supply air sensor Cooling Enabled ClEnbl BI 6 Status that indicates mechanical cooling is enabled Economizer Enabled EcoEnbl BI 15 Status that indicates...

Страница 36: ...setpoint in an hour in the cooling mode This alarm is not used in 100 outside air units or supply air control Control Temperature Heat Failure CtrlTpHF BI 109 This alarm is activated if the control te...

Страница 37: ...Air Temperature RaTp AI 64 Current value of the return tempera ture sensor Space Temperature SpcTp AI 72 Current value of the space tempera ture sensor Supply Air Temperature SaTp AI 83 Current value...

Страница 38: ...e rises one degree above this setpoint the control will activate the cooling demand If the control temperature is the Supply Air Sensor then the cooling demand is always active 0 99 N2 Parameters for...

Страница 39: ...dewpoint in the supply air approximately 10 F above this setpoint 35 70 N2 Parameters for the VCM Controller Parameter Name Object Description Limits Indoor Humidity Setpoint InRhSt AO 120 If the ind...

Страница 40: ...ay 1 ExRly1 BI 133 Current status of relay 6 Expansion Relay 2 ExRly2 BI 134 Current status of relay 7 Expansion Relay 3 ExRly3 BI 135 Current status of relay 8 N2 Parameters for the VCM Controller Pa...

Страница 41: ...d 3 DehumidificationMode 4 ModGasIIConnected 5 ReheatIIConnected 6 N2 Parameters for the VCM Controller Parameter Name Object Description Limits Expansion Relay 4 ExRly4 BI 136 Current status of relay...

Страница 42: ...ts BIT STRING ExpansionBoard3Relay1 0 ExpansionBoard3Relay2 1 ExpansionBoard3Relay3 2 ExpansionBoard3Relay4 3 ExpansionBoard4Relay1 4 ExpansionBoard4Relay2 5 ExpansionBoard4Relay3 6 ExpansionBoard4Rel...

Страница 43: ...PT Link II N2 3 Interface 43 PT Link II N2 3 Technical Guide Notes...

Страница 44: ...TLNK3N2 TGD 01E Printed in the USA October 2016 All rights reserved Copyright 2016 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: