background image

VAV/Zone  Occupied Mode Sequences

31

VAV/Zone Controller Package

  SEQUENCE OF OPERATIONS

  Space Heating Mode

Occupied Space Heating mode is initiated by the temperature in 
the space falling to within 0.5ºF of the Occupied Heating Setpoint. 

If the HVAC unit is in the Supply Air Cooling Mode and another 
VAV/Zone Controller has a heating demand, the damper/airfl ow 
for the VAV/Zone Controller requiring heating will position itself 
to provide the Cooling Minimum amount of air into the space. 
No modulation open will occur because the space does not want 
the cold air currently being supplied by the air handler. 

When  the  HVAC  unit  is  in  the  Occupied  Supply Air  Heating 
Mode, the damper will be held at the Heating Minimum posi-
tion until the space temperature falls to within 0.5ºF of the Oc-
cupied Heating Setpoint.  As the Space Temperature falls below 
the Heating Setpoint, the damper/airfl ow calculation causes the 
air valve to open proportionally until the maximum setpoint is 
achieved at 1.5ºF below the setpoint. This is a 2ºF proportional 
window starting 0.5ºF above the Heating Setpoint to 1.5ºF below 
the Heating Setpoint. 

Two diff erent confi gurations are available for the Occupied Space 
Heating Mode. If the box is confi gured to allow reheat during 
Supply Air  Heating  Mode,  the  reheat  relays  can  be  activated 
even when the HVAC unit is in the Supply Air Heating Mode. 
If the box is confi gured not to allow reheat when the HVAC unit 
is in Supply Air Heating Mode, the box heat relays will be de-
energized when the HVAC unit is in Supply Air Heating mode. 
In either confi guration, when the HVAC unit is in the Supply Air 
Heating Mode, the damper will modulate open proportionally 
to  the  space  demand. The  proportional  window  for  the  space 
temperature is to 1.5ºF below the Heating Setpoint. This allows 
the space to take advantage of the warm supply air in the duct. 

The VAV/Zone Controller can activate auxiliary heating relays. 
Multiple heat stages or modulating heat can activate if the Ex-
pansion Module has been connected and the correct number of 
additional heating stages (2 or 3) has been confi gured. During 
demands for Heat, the fi rst stage will activate whenever the space 
temperature drops below the Heating Setpoint.  The second stage 
will activate if the Space Temperature falls 1.0ºF below the Heat-
ing Setpoint. The third stage will activate if the Space Tempera-
ture falls 2.0ºF below the Heating Setpoint. There is a two-minute 
delay between staging. This prevents stages from activating at 
the same time. Once a Heating Stage has been activated, it must 
remain on for at least one minute. Once it has been deactivated, 
it must remain off  for at least two minutes. The third stage relay 
will deactivate when the Space Temperature rises to within 1.0ºF 
of the Heating Setpoint. The second stage relay will deactivate 
when the Space Temperature rises to the Heating Setpoint. The 
fi rst stage relay will deactivate when the Space Temperature rises 
above the Heating Setpoint by 1.0ºF. See 

Table 3 

for a complete 

layout of the various Fan & Heat relay staging points.

    Modulating ( Proportional) Heat

The   VAV/Zone  Controller  Package  with  the  Zone  Controller 
Expansion Module provides an analog output for control of a 
Modulating Hot Water Valve or SCR Electric Heater. It provides 
a 0-10 VDC signal to control the heating device. When the space 
temperature drops to 0.5ºF above the Heating Setpoint the output 
starts at 0 VDC and ramps up to 10 VDC at 1.5 below the Heat-
ing Setpoint.

   Auxiliary Heat

The Auxiliary Heat option allows for a separate setpoint that is 
diff erent from the other heating setpoints. The Auxiliary Heat 
Relay  energizes  at  0.5ºF  below  the Auxiliary  Heat  Setpoint 
and de-energizes 0.5ºF above the Auxiliary Heat Setpoint. The 
Auxiliary Heat will continue to function regardless of the HVAC 
Mode the Unit controller is in or at any airfl ow condition. This 
is typically used to control baseboard heat or an external duct 
heater.

 

See 

Table 3 

for a complete layout of the various fan and 

heat relay staging points.

 Fan & Reheat Relay Staging

Relays Stage 

On At

Series

Fan

Parallel

Fan

Heat 

Stage 

1

Heat 

Stage 

2

Heat 

Stage 

3

Aux.
Heat

0.5ºF  Above Box 

Heat Setpoint

ON With 

HVAC Fan

*See 

Note 1

X

At Box Heat 

Setpoint

X

1.0ºF  Below Box 

Heat Setpoint

X

2.0ºF  Below Box 

Heat Setpoint

X

0.5ºF  Below 

Aux. Heat 

Setpoint

X

Relays Stage 

Off  At

Series

Fan

Parallel

Fan

Heat 

Stage 

1

Heat 

Stage 

2

Heat 

Stage 

3

Aux.
Heat

1.0ºF  Above Box 

Heat Setpoint

OFF With 

HVAC Fan

See Note 1

X

See 

Note 2

1.0ºF  Above Box 

Heat Setpoint

X

At Box Heat 

Setpoint

X

1.0ºF  Below Box 

Heat Setpoint

X

0.5ºF  Above 

Aux. Heat 

Setpoint

X

NOTES:

:  

1.) If check for main fan status is selected when confi guring the controller, the 
series fan will energize anytime the HVAC unit’s fan is operating, even in the 
unoccupied mode.
2.) The parallel fan will continue to run for 2 minutes following the relay stag-
ing off .

Table 3:    Fan &  Reheat  Relay Staging

Содержание OE326-23I-OR

Страница 1: ...VAV Zone Controller Package Technical Guide www orioncontrols com...

Страница 2: ...101 E mail mail wattmaster com Visit our web site at www orioncontrols com Windows is a registered trademark of Microsoft Corporation Form OR VAVZP TGD 01C All rights reserved August 2018 WattMaster C...

Страница 3: ...d Zone Wiring 24 START UP AND COMMISSIONING 25 Addressing and Baud Rate 25 Initialization and Operator Interfaces 26 Con guring the VAV Zone Controller 27 SEQUENCE OF OPERATION 29 Scheduling Operation...

Страница 4: ...d Room Temperature Sensor wired to the provided 3 position terminal block or an E BUS Digital Room Sensor connected via the integral E BUS cable connector or to the provided 4 position terminal block...

Страница 5: ...002 1002 1002 1002 1002 3650 1002 1002 3650 1002 1002 4751 4751 1002 10uF 001uF 10uF VAC VDC VDE OFF 3650 3650 3650 3650 3650 LO HI REV 1 LO HI SWITCH OCC GND BIN POWER APP HB WDOG OS HB STAT 2 STAT 1...

Страница 6: ...on the actuator cover Pages 10 20 OE282 03 Slaved Zone Damper Kit Includes OE282 Zone Damper Actuator 2 PL101824 Slave Wiring Interface Boards modular cables for controller to actuator connection Used...

Страница 7: ...pad allow for setpoint adjustment override and display of certain status and setpoints The OE217 02 is used with the VAV Zone Controller for room air temperature sensing applications Typically hard wi...

Страница 8: ...hardware for ush mounting into hollow drywall or surface mounting on concrete brick or plaster surfaces Includes SMTS L with 12 ft long pigtail cable assembly See the SMTS L Technical Guide OE391 12 M...

Страница 9: ...DRV NET DRV PIC32 MLPD YS102398 REV 3 NETWORK LOCAL PD COMM POWER 1 2 4 8 16 32 COMM ADDRESS ML PD MADE IN USA SERIAL C22 C23 C30 C37 C40 J1 J3 R1 R2 R3 R4 R20 R21 R22 R23 R24 R25 R26 R27 R31 PDSTAT1...

Страница 10: ...POLARITY MUST BE OBSERVED OR THE CONTROLLER WILL BE DAMAGED POWER INPUT E BUS CONNECTORS GND GND SH GND BIN TMP R T 24 VAC DUCT TEMP SENSOR OCCUPIED SWITCH COMM 1 1 2 ADDRESS ON 2 4 8 16 32 BAUD ADDRE...

Страница 11: ...ctuator 0 38 5 70 4 15 3 00 0 75 2 Modular Cables 18 0 Figure 5 OE736 03 PT P D Rectangular Damper Kit with Terminal Blocks 15 50 14 15 Dimensional Info Component View Damper Actuator Enclosure Base E...

Страница 12: ...Control Base Cover 1 2 Foil Face Insulation Damper Housing Damper Blade And Shaft 11 5 12 0 1 2 Foil Face Insulation Damper Housing Damper Blade And Shaft Air Flow Pickup Cross Control Base Cover P I...

Страница 13: ...the 2 shaft mounting bracket nuts on the ends of the damper actuator s shaft mounting U bolt and slide damper actua tor assembly over the terminal unit damper shaft The actuator may have to be rotated...

Страница 14: ...e s per the instructions Failure to size the transformer and or wire the Non Modular VAV Zone Controller Package s correctly may cause the VAV Zone Controller Package to operate erratically or not at...

Страница 15: ...e complete apply power to the transformer s that is connected to the VAV Zone Controller Powering Up When the Controller and Modules are rst powered up the POWER LED should light up and stay on contin...

Страница 16: ...age drop 18ga wire 0 00054 voltage drop per 1 length of wire 16ga wire 0 00034 voltage drop per 1 length of wire 14ga wire 0 00021 voltage drop per 1 length of wire For our example we will use 18 gaug...

Страница 17: ...P1 R5 TB4 TB3 SW1 R5 R5 R4 R4 R4 R4 R4 R37 R24 R21 R14 R13 R11 R10 R6 R5 R4 P3 D7 C25 C15 C5 C4 J1 R42 C29 D13 3650 D9 WattMaster Label L 102202 Rev 1A B RELAY CONTACT RATING IS 1 AMP MAX 24 VAC AUXIL...

Страница 18: ...detected contacts shorted together for the Occupancy Detection Time period the control ler will display Occupied Mode and control to the Occupied Cooling and Heating setpoints If no motion is detecte...

Страница 19: ...ntroller Expansion Module Inputs and Outputs Other Connections E BUS Connectors The EBC E BUS modular connectors are used to connect the optional OE325 03 VAV Zone Controller Expansion Module to the V...

Страница 20: ...VAV Zone Controller Package Wiring Figure 10 VAV Zone Controller Package with Terminal Blocks Wiring 20 VAV Zone Controller Package INSTALLATION WIRING...

Страница 21: ...VAV Zone Controller Expansion Module Wiring 21 VAV Zone Controller Package INSTALLATION WIRING Figure 11 VAV Zone Controller Expansion Module Wiring Fan Terminals And Or Electric Staged Heat...

Страница 22: ...oad Connect to VAV Zone Controller E BUS Female Connector Connect to VAV Zone Controller E BUS Female Connector RC R1 Figure 13 VAV Zone Controller Expansion Module Wiring Fan Terminals And Or On O HW...

Страница 23: ...VAV Zone Controller Expansion Module Wiring Figure 14 VAV Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 23 VAV Zone Controller Package INSTALLATION WIRING...

Страница 24: ...LAVE INTERFACE YS101824 TO ACTUATOR OPEN CLOSE FDBK OPEN GND GND PJ1 PJ2 LD2 LD1 OPEN CLOSE CLOSE TB1 TB2 FROM ZONE CONTROLLER BYPASS AND SLAVE INTERFACE YS101824 TO ACTUATOR OPEN CLOSE FDBK OPEN GND...

Страница 25: ...OLLER WILL BE DAMAGED POWER INPUT E BUS CONNECTORS GND GND SH GND BIN TMP R T 24 VAC DUCT TEMP SENSOR OCCUPIED SWITCH COMM 1 1 2 ADDRESS ON 2 4 8 16 32 BAUD ADDRESS SWITCH www wattmaster com OE326 23D...

Страница 26: ...he next step is con guring the controller for your speci c re quirements In order to con gure the VAV Zone Controller you must use an operator interface Four di erent operator interfaces are available...

Страница 27: ...on allows you to calibrate the box CFM correctly using the box manufacturer s K factor Enter the correct K CFM factor for the inlet diameter of the box you are con guring See the K factor table that f...

Страница 28: ...Supply Air Heating Mode This setpoint temperature can be set higher or lower than the Space Heating Setpoint NOTE This setpoint follows the Unoccupied Heating Setpoint Setback Auxiliary Heat The Auxi...

Страница 29: ...10 seconds will cancel the override Digital Room Sensor Pushing the override button momentarily initiates the override which will continue for a con gurable duration of time 0 8 hours If during the ov...

Страница 30: ...moves to during the Unoc cupied mode When using non fan powered terminal units the VAV Zone damper will position itself in the Night Minimum position In order for fan powered terminal units to positio...

Страница 31: ...the Space Tempera ture falls 2 0 F below the Heating Setpoint There is a two minute delay between staging This prevents stages from activating at the same time Once a Heating Stage has been activated...

Страница 32: ...want the warm air currently being supplied by the air handler When the HVAC unit is in the Unoccupied Supply Air Cooling Mode the damper will be held at the Night Minimum Position until the Space Temp...

Страница 33: ...Tempera ture falls 2 0 F below the Heating Setpoint There is a two minute delay between staging This prevents stages from activating at the same time Once a heating stage has been activated it must r...

Страница 34: ...tegral is not included 1 F is half of the 2 F Proportional Window If you had set the Integral to 1 0 the calculation would add 2 to the current damper air ow calculation each time The calcula tion occ...

Страница 35: ...ly properly operating zones can have an e ect on the HVAC Mode calculation The zone has not been reported as Missing The zone is not currently undergoing Damper Calibration The zone damper does not ha...

Страница 36: ...l be generated High Space Temp Alarm If the zone temperature is above the Cooling Setpoint by the High Zone Alarm O set user adjusted for the Zone Alarm Delay Period user adjusted this alarm will be g...

Страница 37: ...to broadcast the time so that the VAV Zone Controllers can read it and use it in their tenant and trend logs CAUTION These logs are subject to loss if a power outage occurs Internal Trend Logs Force M...

Страница 38: ...rity Only the highest priority failure code will blink You must correct the highest priority alarm before other problems will be indicated LED Blinks This Number of Times Blink Code Description 1 Norm...

Страница 39: ...Temperature Sensor by measuring the resistance or voltage using a digital multimeter Set the meter to DC Volts Place the positive probe on the AIN terminal and the negative probe on the GND terminal...

Страница 40: ...efective actuator If this solves the problem the defective actua tor will need to be replaced Diagnostics VAV Zone Controller Expansion Module If the VAV Zone Controller Expansion Module does not seem...

Страница 41: ...7 R18 C20 D4 R17 D6 D7 R32 R33 D5 1 J1 DISP1 C15 D2 R2 R5 R7 R16 R19 R20 U6 U2 TB2 R35 2 2uF R18 1002 1001 1330 4751 4751 1001 1001 1uF 9 21Mhz 4751 4751 LTC3502 1uF 15pF 6 8uF 1uF 10uF 3162 1502 6 8u...

Страница 42: ...3 160 58 15385 3 100 60 14681 3 042 62 14014 2 985 64 13382 2 927 66 12758 2 867 68 12191 2 810 69 11906 2 780 70 11652 2 752 Temperature Resistance Voltage for Type III 10 K Ohm Thermistor Sensors Te...

Страница 43: ...h local loop allows up to 16 VAV Zone Controllers can be con gured as voting zones and additional controllers to be non voting zones ForVAVsystems you can have up to 58 total VAV Zone Controllers in a...

Страница 44: ...ACTUATOR HEAT AUX COMM ADDRESS DUCT SENSOR GND 12V DIGITAL SENSOR SPACE GND ADJ TMP 1 2 4 8 16 32 CW CCW ON LOOP BAUD 1 2 3 3V 5 0V AIRFLOW TP GND YS102588 SERIAL E BUS V4 V3 R60 R59 C34 TB1 R30 R29...

Страница 45: ...CT RATING IS 1 AMP MAX 24 VAC AUXILIARY HEAT ACTUATOR CONNECTOR DIGITAL SPACE SENSOR ANALOG SPACE SENSOR GND GND 12 VDC ADJ TMP HEAT COM 24 VAC POWER ONLY WARNING POLARITY MUST BE OBSERVED OR THE CONT...

Страница 46: ...STAT 1 ACTUATOR HEAT AUX COMM ADDRESS DUCT SENSOR GND 12V DIGITAL SENSOR SPACE GND ADJ TMP 1 2 4 8 16 32 CW CCW ON LOOP BAUD 1 2 3 3V 5 0V AIRFLOW TP GND YS102588 SERIAL E BUS V4 V3 R60 R59 C34 TB1 R...

Страница 47: ...ck 19 Communication Wiring 17 Connection Diagram Slaved Zone 24 Controller Voltage and Environment Requirements 14 27 Controller Addressing 25 Cooling Minimum 29 Cooling Only Box 27 Counterclockwise t...

Страница 48: ...1 22 Modulating HW Heat 22 Modulating Proportional Heat 31 33 Motion Sensor Occupancy Detection 18 28 Mounting 13 Multiple Daily Setpoints Schedules 27 Multiple Loop VAV Zoning 43 N Networked Multiple...

Страница 49: ...ts 19 Staging 31 Resistance Testing Digital Room Sensor 41 Modular Room Sensor 41 Round Damper 7 Round Damper Kit 12 Dimensions 12 Mounting 13 S Scheduling 29 SCR Electric Heat 23 Sensors Mounting 13...

Страница 50: ...Expansion Module 6 Dimensions 10 Inputs 18 Outputs 19 Troubleshooting 40 Wiring 21 22 23 VAV Zone Controller Package 5 Mounting 13 Wiring 20 VAV Zone Controller System Architecture 43 VAV Zone Damper...

Страница 51: ...VAV Zone Controller 51 NOTES VAV Zone Controller Package...

Страница 52: ...rm OR VAVZP TGD 01C Printed in the USA August 2018 All rights reserved Copyright 2018 AAON Controls 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816 505 110...

Отзывы: