7 Setting
-
42
-
7.3 Operating
current
Use the current setting switch “SW1” to set the actuator’s operating current.
Set the operating current as a product of the maximum driver output current “F,”
which is 100%, multiplied by the operating current percentage corresponding to the
given dial.
The switch provides a selection of 16 levels ranging between “0” and “F.”
If there is extra torque, the current may be set to a lower level in order to suppress
increases in motor temperature.
Factory setting
[F]: Driver’s maximum
output-current value
Current setting switch
(SW1)
SW1
The dial settings and corresponding levels of operating current rates are as follows:
Dial
setting
Operating
current rate [%]
Dial
setting
Operating
current rate [%]
0 6 8 56
1 13 9 63
2 19 A 69
3 25 B 75
4 31 C 81
5 38 D 88
6 44 E 94
7 50 F 100
Note
An excessively low operating current level may cause a problem when
starting the actuator or holding the load in position. Do not reduce the
current any more than is necessary.