Installation Manual:
AdvanTex
®
AX20-RT Treatment Units
NIM-ATX-AXRT-1
Rev. 1.0, 1/10
© 2010 Orenco Systems
®
Inc.
13
Step 10: Install and Test Control Panel (cont.)
Step 10h:
Refer to the control panel documentation to test the
floats that activate/deactivate the pump. To perform the float test,
make sure there is enough liquid in the tank. If there isn’t enough
liquid in the tank, turn the pump circuit breaker off.
NOTE:
If phone service to the panel is active, complete step 10i.
If not, proceed to step 10j. However, phone service should be
activated before system start-up.
Step 10i:
Press and release the “Push-To-Silence” button 15
times within a one-minute period. This instructs the panel to call
the VeriComm Monitoring System.
• A red LED (“Modem Activity” component) should illuminate, indicat
-
ing that the controller has established communication with the host.
(This may take a few minutes.)
• Once the communication session has ended, the modem will auto
-
matically disconnect.
• If the LED does not illuminate within the specified time, verify that the
phone line has a dial tone. This can be done by hooking up a phone
to the line that is going into the panel.
Step 10j:
The panel will automatically disable Test Mode and
return to normal operation after 30 minutes. To disable Test
Mode manually, hold the “Push-To-Silence” button on the front
of the panel until the audible alarm sounds (approximately 15
seconds). The appropriate digital input should be illuminated
when the “Push-To-Silence” button is held in. When the audible
alarm sounds to indicate that the panel is no longer in Test Mode,
release the button.