Sun Network QDR InfiniBand Gateway Switch Service Manual for Firmware Version 2.1 • March 2013
2. Access the Oracle ILOM CLI.
See
“Access the Oracle ILOM CLI (NET MGT Port)” on page 35
.
3. Verify that the battery is faulty.
a. Type.
If the battery is faulty, you will see
/SYS/MB
listed in the output under
Target:
.
For example:
b. Note the number to the left of
/SYS/MB
.
c. Type.
where
number
is the number to the left of
/SYS/MB
. For example:
->
show -d targets /SP/faultmgmt
->
show -d targets /SP/faultmgmt
/SP/faultmgmt
Targets:
0 (/SYS/MB)
->
->
show -d properties /SP/faultmgmt/
number
/faults/0
->
show -d properties /SP/faultmgmt/0/faults/0
/SP/faultmgmt/0/faults/0
Properties:
class = fault.chassis.device.battery.low
sunw-msg-id = DCSIB-8000-45
uuid = 82e90599-8650-47dc-b613-1e602607441b
timestamp = 2002-01-01/00:07:27
fru_part_number = 3002234
fru_serial_number = 006541
product_serial_number = AK00022680
chassis_serial_number = AK00022680
->