Installing the Switch
89
3. Repeat
for the other CMC.
4. Verify the power supply status.
See
“Verify the Power Supply Status” on page 89
.
Related Information
■
Switch Command Reference
,
fruinfo
command
■
“Display the Power Supply FRU ID Information” on page 91
■
“Display the Fabric Card FRU ID Information” on page 100
■
“Display the Line Card FRU ID Information” on page 107
■
“Display the InfiniBand Cable FRU ID Information” on page 118
▼
Verify the Power Supply Status
1. Identify the prerequisite and subsequent tasks you must perform in
conjunction with this procedure, to install the switch.
See the table in
“Installation Sequence” on page 20
2. On the CMC, type:
where
slot
is the number of the power supply from
0
to
3
.
For example, to check the status of power supply 0:
3. If any power supply is not producing 12V, investigate why.
See
“Check the Power Supply Status LEDs” on page 80
4. Consider your next step:
Multi Record Area:
PICMG Board Point-to-Point Connectivity Record (ID=0x14)
Version = 0
Record Type = 0xc0 OEM Defined Record
Version = 2
PPS IPMB Topology Record (ID=0x05)
Version = 0
#
#
psustatus
slot
#
psustatus 0
PSU 0, 12 V on
#