Sun Datacenter InfiniBand Switch 648 Installation Guide • May 2010
14. Repeat
through
for each fabric card to be installed.
Install the cards into the following slots in the given sequence:
0, 1, 8, 7, 6, 2, 3, 5, 4
15. Repeat
through
for each fabric card filler, installing the fillers into
the vacant slots.
16. Remove the midplane stiffener.
See
“Remove the Midplane Stiffener” on page 70
Related Information
■
Switch Service
, servicing fabric cards
■
“Fabric Card Distribution” on page 17
■
“Install the Midplane Stiffener” on page 64
■
“Suggested Tools for Installation” on page 19
▼
Remove the Midplane Stiffener
You must remove the midplane stiffener before installing the line cards.
1. Identify the prerequisite and subsequent tasks you must perform in
conjunction with this procedure, to install the switch.
See the table in
“Installation Sequence” on page 20
.
2. Using a 20 mm socket and ratchet, turn the left retainer bolt 1/4 turn
counter-clockwise.