Preparing the Site
45
Related Information
■
“Airborne Contaminates” on page 45
■
“Heat Dissipation and Airflow Requirements” on page 47
■
“Cooling Airflow From Ceiling Vents” on page 49
■
“Cooling Airflow From Perforated Floor Tiles” on page 50
■
“Measure the Ambient Temperature and Humidity” on page 52
Airborne Contaminates
Excessive concentrations of certain airborne contaminants can cause the server’s
electronic components to corrode and fail. Take measures to prevent contaminants
such as metal particles, atmospheric dust, solvent vapors, corrosive gasses, soot,
airborne fibers, or salts from entering, or being generated within, the data center.
Avoid locating the data center near print rooms, machine shops, wood shops, loading
docks, and areas that involve the use of chemicals or generate toxic vapors or dust.
Ensure the exhaust from generators or other sources of exhaust do not enter the
intakes of air conditioning systems serving the data center. If the data center must be
located near these hazardous locations, add and regularly maintain adequate filtering
systems.
Note –
To avoid introducing airborne contaminates to the data center, unpack the
server outside of the data center and then move the server to its final location.
Vibration
0.15G (vertical), 0.10G (horizontal),
5 to 500 Hz, swept-sine
0.5G (vertical), 0.25G (horizontal),
5 to 500 Hz, swept-sine
Shock
3.0G, 11 ms, half-sine
Roll-off:
1-inch roll-off free fall,
front-to-back rolling directions
Threshold:
25 mm threshold height at
0.75m/s impact velocity
Incline
5 degrees max. (9% grade max.)
5 degrees max. (9% grade max.)
Requirement
Operating Range
Nonoperating Range
Optimum Range
Содержание sparc M5-32
Страница 1: ...SPARC M5 32 and SPARC M6 32 Servers Installation Guide Part No E41215 05 December 2014 ...
Страница 8: ...viii SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 16: ...6 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 Front Components ...
Страница 18: ...8 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 Rear Components ...
Страница 21: ...Understanding the Server 11 FIGURE DCU Locations Rear of Server ...
Страница 43: ...Preparing the Site 33 FIGURE 4 Wire Power Cord AC Plug 460P9W Figure Legend 1 L1 2 L2 3 L3 4 Ground ...
Страница 51: ...Preparing the Site 41 ...
Страница 82: ...72 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 106: ...96 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 182: ...172 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...