50
SPARC M5-32 and SPARC M6-32 Servers Installation Guide • December 2014
Cooling Airflow From Perforated Floor Tiles
If you install the server on a raised floor and you provide underfloor cooling, install
perforated tiles in front of the server to cool it.
The following illustration shows an example arrangement of seven perforated floor
tiles providing cooling air to the server. In this example, each perforated tile provides
600 CFM of cooling air in order to provide the 4200 CFM maximum total cooling
airflow.
If your perforated floor tiles provide cooling air greater than 600 CFM, you can use
fewer tiles to cool the server. For example, if the perforated floor tiles produce 700
CFM of cooling air, install six floor tiles in front of the server.
Note –
The exact arrangement of these floor tiles depends on the space available in
front of your server. Contact your facility manager for information about the proper
arrangement of these tiles for your facility.
Содержание sparc M5-32
Страница 1: ...SPARC M5 32 and SPARC M6 32 Servers Installation Guide Part No E41215 05 December 2014 ...
Страница 8: ...viii SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 16: ...6 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 Front Components ...
Страница 18: ...8 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 Rear Components ...
Страница 21: ...Understanding the Server 11 FIGURE DCU Locations Rear of Server ...
Страница 43: ...Preparing the Site 33 FIGURE 4 Wire Power Cord AC Plug 460P9W Figure Legend 1 L1 2 L2 3 L3 4 Ground ...
Страница 51: ...Preparing the Site 41 ...
Страница 82: ...72 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 106: ...96 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...
Страница 182: ...172 SPARC M5 32 and SPARC M6 32 Servers Installation Guide December 2014 ...