Preparing the Site
49
Cooling Airflow From Ceiling Vents
When cooling the data center using ceiling vents, install the vents in front of the
server so that conditioned air flows through the server. To provide maximum
cooling, the airflow should be approximately 4200 CFM.
Related Information
■
“Heat Dissipation and Airflow Requirements” on page 47
■
“Cooling Airflow From Perforated Floor Tiles” on page 50
■
“Measure the Ambient Temperature and Humidity” on page 52
1
Front of server
2
Rear of server