CHAPTER 3: CONFIGURING A CONTROL SYSTEM
SNAP PAC Redundancy Option User’s Guide
25
25
7.
Using the IP addresses you created earlier, enter the IP address for Controller 1, Controller 2, and
the Arbiter, then click OK.
For information on assigning IP addresses, see
“Assigning a Primary IP Address to ENET 1 on
and
“Assigning an IP Address to the Arbiter” on page
The completed dialog box will look something like this:
8.
For Controller Port, Software Retries, and Software Timeout, use the default settings:
Controller Port: 22001
Software Retries: 0
Software Timeout: 5000 msec
9.
Click OK, and then exit PAC Terminal.
10.
In PAC Redundancy Manager, under Redundant Control Engines, click Refresh.
The control engine you created with redundant controllers appears under Redundant Control
Engines.
New redundant
control engine