APPENDIX B: TROUBLESHOOTING
B1 and B2 User’s Guide
27
27
labeled UPPER (closest to module), and if the module has terminals on the top of the
module, connections would be made there. Analog racks have the terminal channels
labeled from 1 to 4 (or 16). These channels correspond to module positions 0 to 3 (or 15)
respectively.
f.
If all inputs on that board have the same -4,096 reading, then check to make sure the board
has +15 and -15 VDC at the corresponding terminals (with reference to the terminal that is
marked COMMON).
Q.
I receive a large number of checksum errors (N02) when I send commands to an Optomux unit.
A.
Make sure that you are using twisted pair cable. The RS-422/485 network is only reliable when
the communications cable is twisted (+ and - lines of EACH pair twisted together) with at least 1/2
twist per inch. Sometimes, the wire is twisted but one of the connections of a pair is actually used as
the mate to the opposite pair ( - of one pair used as - of opposite pair). This cross-twist condition is
usually due to jacketed twisted pair cables, which have a wire of each pair with the same color code.
In this case, strip the jacket back far enough to properly identify the individual pairs.
You should also check the Group A jumpers to make sure the termination and bias jumpers are
correctly installed.
Содержание Optomux B1
Страница 1: ...B1 AND B2 USER S GUIDE Form 1574...
Страница 9: ...FOR HELP B1 and B2 User s Guide 4...
Страница 26: ...CHAPTER 3 INSTALLATION AND WIRING B1 and B2 User s Guide 21 21 Figure 2 7 Jumper Addresses...
Страница 29: ...SURGE PROTECTION FOR RS 422 485 COMMUNICATION LINKS B1 and B2 User s Guide 24...
Страница 33: ...TROUBLESHOOTING QUESTIONS AND ANSWERS B1 and B2 User s Guide 28...