background image

TROUBLESHOOTING QUESTIONS AND ANSWERS

B1 and B2 User’s Guide

26

Q.

 I send a command to activate several outputs. The Optomux unit responds with no error, but 

none of my outputs come on. 

A.

 If an output does not turn on, check the following:

a.

Make sure you configured the outputs of the Optomux unit correctly. The unit defaults to 
all positions configured as inputs on power-up.

b.

If power was lost at any time and returned, the unit will have lost its configuration. The unit 
will have reported a N00 error to the first command sent after the power-up to indicate 
that configuration was lost.

c.

If using a digital Optomux unit, make sure you are using output modules with a 5 VDC logic 
voltage (OAC5, ODC5, etc.). Sometimes modules with a 15 VDC or 24 VDC logic voltage 
(ODC15, OAC24, etc.) are inserted by mistake. The LED may turn on or be dim with the 15 
VDC and 24 VDC modules, but there will be no output on the field side.

d.

If the output LED is on, but the load does not turn on, check the field voltage and wiring. 
Also, the load may not draw enough current to meet the minimum current requirements 
of OAC5 modules (20 mA).

Q.

 I send a command message to an Optomux unit at address 0, and I get no response. However, 

the Optomux’s REC light flashes.

A.

 The receive lights on all the Optomux boards wired in a multidrop mode should light whenever a 

command is sent. Only the unit at the address that matches the command message address should 
respond. When an Optomux unit responds, the XMT (transmit) light will flash. At high baud rates, 
and for messages with only a short response (“A” only), the flash will be so brief it may be missed 
visually.

If the host receives no response, and no flash of the XMT light is visible at the slowest baud rate 
(300), then check the following:

a.

Make sure the address in the command message matches the Optomux address. Check 
the jumpers. A common mistake is a reversal of jumpers. All address jumpers (B0 through 
B7) installed are address 0, and all address jumpers (B0 through B7) removed corresponds 
to address 255. 

b.

Make sure the baud rate is correct between the host and the Optomux unit. All Optomux 
units on the same link should be configured to the same baud rate.

c.

Make sure you have a solid +5 volts powering the Optomux unit. If the voltage is too low, 
the RCV light may flash, but the unit will not be able to respond. Measure the voltage at the 
unit’s power terminals — not at the power supply.

d.

Check to make sure the communications link is wired with the correct polarity and that the 
A group of jumpers is configured correctly.

Q.

 When I read position 3 of an Optomux analog board, I receive a 0000, which converts to a 

decimal -4,096 value when I subtract the 1,000 hex offset.

A.

 A -4,096 decimal reading may indicate one of the following:

a.

You are reading a module position that has no input module installed.

b.

You are reading a thermocouple module that has no thermocouple installed, or the 
thermocouple probe is open.

c.

An ICTD module has the ICTD wired in reverse.

d.

A 4–20 mA module is wired with reverse polarity.

e.

The field connections are made to the wrong terminals. Field connections vary with each 
module. Refer to the module’s data sheet for information on wiring each specific module. 
In general, field connections made to the terminals on the rack are made to the terminals 

Содержание Optomux B1

Страница 1: ...B1 AND B2 USER S GUIDE Form 1574...

Страница 2: ...siness Park Drive Temecula CA 92590 3614 Phone 800 321 OPTO 6786 or 951 695 3000 Fax 800 832 OPTO 6786 or 951 695 2712 www opto22 com Product Support Services 800 TEK OPTO 835 6786 or 951 695 3080 Fax...

Страница 3: ...1142245 French Patent No 1142245 British Patent No 1142245 Japanese Patent No 2002535925A German Patent No 60011224 Opto 22 FactoryFloor Optomux and Pamux are registered trademarks of Opto 22 Generati...

Страница 4: ...6 Modular Construction 6 Wiring 7 Data Transmission 7 System Throughput 7 Features 8 Digital Optomux 8 Latched Inputs 8 Time Delays 8 Pulse Generation 9 Event Counting 9 Pulse Duration Timers 9 Analo...

Страница 5: ...Supply 15 Third Party Power Supply Vendors 17 Brain Board Mounting 18 Selecting the Jumpers 19 Group A Jumpers 19 Group B Jumpers 19 Baud Rate Selection 20 Protocol Selection 20 Address Selection 20...

Страница 6: ...rial port with an RS 485 converter up to 4095 I O points can be accessed over a distance of several thousand feet at moderate speeds with high reliability NOTE B1 and B2 brain boards offer serial comm...

Страница 7: ...alic typeface indicates emphasis and is used for book titles Example See the OptoControl User s Guide for details File names appear in all capital letters Example Open the file TEST1 TXT Key names app...

Страница 8: ...hnical support be prepared to provide the following information about your system to the Product Support engineer Software and version being used Controller fi rmware version PC confi guration A compl...

Страница 9: ...FOR HELP B1 and B2 User s Guide 4...

Страница 10: ...ined on the same serial link providing endless combinations of analog and digital I O points Optomux I O units communicate with the host computer over an RS 485 serial communications link The serial d...

Страница 11: ...units consists of two twisted pairs and a common which makes it practical to have an Optomux located at each machine on a factory floor at each heating or air conditioning unit in an energy managemen...

Страница 12: ...st by Optomux for verification before it can be executed After the host verifies that the two messages are identical an execute command gives Optomux the go ahead the required action is performed and...

Страница 13: ...ts by functioning as latches Each input position can be configured by host command to latch on either OFF to ON or ON to OFF transitions The host computer can recall and or clear the status of these l...

Страница 14: ...n of 10 milliseconds Analog Optomux In addition to simple input and output B2 Optomux units perform Analog Input Averaging The B2 can be instructed to average the values of successive readings High Lo...

Страница 15: ...s Choose a baud rate and protocol compatible with your host computer and make this information available to the hardware installer The installer will need it to set the jumpers on each controller Assi...

Страница 16: ...wo pairs for the data and use one of the wires from an extra pair for the signal common The signal common should not be connected to ground Connect the overall cable shield to ground in one location o...

Страница 17: ...n adjacent Optomux units on the serial link The Optomux unit at the end of the data link has only 5 wires To Host From Host and common HINT Always think of the previous Optomux units as the host Figur...

Страница 18: ...barrier strip terminals on the I O mounting rack When connecting DC loads or input the lower numbered terminal is always more positive For detailed information concerning module specifications and wir...

Страница 19: ...ion Secure the module with the captive Phillips head screw Refer to the module s data sheet for detailed specifications and wiring diagrams for each analog I O module Figure 2 4 Analog Mounting Rack 3...

Страница 20: ...can be used to provide power to digital Optomux units The power supply attaches to the I O mounting rack beneath the removable brain board portion of the Optomux unit Connecting the Power Supply Conne...

Страница 21: ...floating or are connected to RS 485 adapter card without proper biasing the RX and TX LED lights may float to an unknown state This may cause confusion as to the actual state of the communication lin...

Страница 22: ...Santa Ana CA 92705 714 979 4440 POWER ONE 740 Calle Plano Camarillo CA 93010 805 987 8741 POWER GENERAL 152 Will Drive P O Box 189 Canton MA 02021 617 828 6216 SOLA 1717 Busse Hwy Elk Grove Village IL...

Страница 23: ...the digital brain board B1 should be such that the brain board extends away from the rack The orientation of the analog brain board B2 is such that the brain board covers up the communications and pow...

Страница 24: ...lled as follows X INSTALLED Install jumper A0 and A6 if the Optomux unit is the last unit in the serial data link For repeat mode settings all Optomux bus should be jumpered as follows Group B Jumpers...

Страница 25: ...mpers B0 through B7 select the Optomux address Each Optomux unit on the same network must have a unique address different from all the others Addresses are arbitrary and do not need to be sequential a...

Страница 26: ...CHAPTER 3 INSTALLATION AND WIRING B1 and B2 User s Guide 21 21 Figure 2 7 Jumper Addresses...

Страница 27: ...ptomux network The AC7A is for 120 VAC operation and the AC7B is for 240 VAC operation AC8 This serial adapter card converts a half duplex RS 232 serial port to a full duplex RS 422 485 port The adapt...

Страница 28: ...otection Surge Protection For RS 422 485 Communication Links For more information or for catalog requests contact Phoenix Contact Inc P O Box 4100 Harrisburg PA 17111 0100 E mail info phoenixcon com P...

Страница 29: ...SURGE PROTECTION FOR RS 422 485 COMMUNICATION LINKS B1 and B2 User s Guide 24...

Страница 30: ...an Optomux unit at address 255 and output 4 goes on A Module positions are numbered from 0 to 15 Therefore the fifth bit in the bitmask is for position labeled 4 Following are the bitmask values for...

Страница 31: ...hort response A only the flash will be so brief it may be missed visually If the host receives no response and no flash of the XMT light is visible at the slowest baud rate 300 then check the followin...

Страница 32: ...ksum errors N02 when I send commands to an Optomux unit A Make sure that you are using twisted pair cable The RS 422 485 network is only reliable when the communications cable is twisted and lines of...

Страница 33: ...TROUBLESHOOTING QUESTIONS AND ANSWERS B1 and B2 User s Guide 28...

Отзывы: