G4LC32ISA-LT User’s Guide
3-5
If COM0 or COM1 is configured for RS-232 communication, jumpers B0–B8 for COM0, or jumpers
C0–C8 for COM1. These must be installed for proper operation.
Table 3-2: Biasing and Termination Jumpers
Jumper
Description
B0 or C0
Pull-up for TX/RX+ (BIAS)
B1 or C1
Terminator for TX/RX
B2 or C2
Pull-down for TX/RX- (BIAS)
B3 or C3
Pull-up for RX+ (BIAS)
B4 or C4
Terminator for RX line
B5 or C5
Pull-down for RX- line (BIAS)
B6 or C6
Pull-up for IRQ+
B7 or C7
Terminator for IRQ
B8 or C8
Pull-down for IRQ-
B jumpers are for COM0; C jumpers are for COM1