27
9. Warranty
Warranty on this product is valid against defects in material and workmanship
for a period of 24 months from its original date of purchase.
10. Technical Specifications
10.1 Power Range 1000-3000 VA (100/110/120V)
GENERAL
Rated power
1000 VA, 1500VA, 2000 VA, 3000 VA at p.f 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase:
Single phase with ground
Bypass Voltage
96--138 VAC (user selectable)
Input Voltage range:
60/70/80VAC-144 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
1000 VA 8.2A, 1500 VA 12.3A, 2000 VA 16.5A, 3000 VA 24.7A
Input Power factor:
0.97
OUTPUT
Output Voltage:
100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation
± 0.25 Hz (battery or free running mode)
* 60V at 40% load, 70V at 70%, 80V at 100%.
ENVIRONMENTAL
Ambient temperature:
+0 °C to +40 °C
Recommended temperature:
+15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling: Forced
air-cooling
Humidity: 0-95%,
non-condensing
Audible noise:
< 40 db normal and battery mode
10.2 Power Range 1000-3000 VA (220/230/240V)
GENERAL
Rated power
1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f. 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase
Single phase with ground
Bypass Voltage:
184-265 VAC (user selectable)
28
Input Voltage range:
120/140/160 VAC-276 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
1000 VA 4A, 1500 VA 6A, 2000 VA 7.7A, 3000 VA 12A
Input Power factor:
0.97
OUTPUT
Output Voltage:
208/220/230/240 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load
Frequency regulation
± 0.25 Hz (battery or free running mode)
* 120V at 40% load, 140V at 70%, 160V at 100%.
Dynamic response:
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity:
100-125% 1 min, 125-150% 10 sec
Efficiency:
greater than 86%
ENVIRONMENTAL
Ambient temperature:
+0 °C to +40 °C
Recommended temperature:
+15 °C to +25 °C
Storage temperature:
-15 °C to +50 °C
Cooling: Forced
air-cooling
Humidity: 0-95%,
non-condensing
Audible noise:
< 40 db normal and battery mode
10.3 Power Range 1000-3000 VA (100/110/120V 19” Rack-mount
model)
GENERAL
Rated power
1000 VA, 1500 VA, 2000 VA, 3000 VA at p.f. 0.7
Technology
On-line, double conversion topology with automatic bypass
INPUT
Phase:
Single phase with ground
Bypass Voltage
96--138 VAC (user selectable)
Input Voltage range:
60/70/80VAC-144 VAC
Frequency:
50/60 Hz. Auto selection
Frequency window from mains
45-65 Hz
Synchronization window
± 3Hz.
Input current
1000 VA 8.2A, 1500 VA 12.3A, 2000 VA 16.5A, 3000 VA 24.7A
Input Power factor:
0.97
OUTPUT
Output Voltage:
100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation:
± 2%
Voltage distortion:
< 5% THD at full non-linear load, < 3% THD at full linear load