17
USB port
Connecting the UPS to your computer is accomplished through the USB port on the back of
your computer. USB compliant hardware and operating system will be necessary including
installation of a UPS driver. The serial port cannot be used when using the USB port.
6.1 EPO port (emergency power off)
A customer-supplied switch located remotely can be used to open the EPO connection and
allows UPS output receptacles to be switched off. Since the EPO shuts down the equipment
immediately, orderly shutdown procedures are not followed and not by any power
management software. The UPS will have to be manually restarted in order to regain power
to the outlets.
6.2 Data Line protection (1000 - 3000 VA)
The network transient protector, located on the back panel, has both IN and OUT jacks, and
houses a single RJ-45 (10BaseT) network connector or RJ-11 telephone line connector.
Connect the input connector to the jack labeled IN, and the output connector to the jack
labeled OUT.
6.2 Load segments (1000 - 3000 VA)
The power management software controls the sets of receptacles known as load segments
which provides organized shutdown and startup of the equipment. Less critical equipment
can be turned off during power outages saving battery power for critical loads. The power
management software manual has more details regarding this. The load group status can be
viewed from the LCD display and can be changed if necessary. These load segments are
usually handled with the UPS management software. Refer to chapter 5.2 regarding the two
load segments that come with each model.
18
7. User’s guide to operations
Necessary information for operation of the unit is covered in this chapter.
Normally the UPS runs automatically, but on those few occasions such as just
after installation, all the starting and shutting down procedures are described
herein.
7.1 Starting and shutting down the UPS
Starting the UPS
z
Ensure that installation was correct and successful and that the input power cable is
connected to a well-grounded outlet.
z
The UPS can be started by pushing the “ON/OFF” button on the front panel.
z
The UPS should now start its inspection of: internal functions, main synchronization and
inverter startup. Then power should start to be supplied via the outlets.
z
During this inspection, the LCD will display “Ready on”. The LED shall light up when
output power has commenced and the LCD will display “Line mode”.
z
Switch on the loads.
Shutting down the UPS
z
Shut down and turn off the loads.
z
Push the “ON/OFF” button on the front panel for five seconds. The alarm will sound and
the UPS will shut down.
z
The LCD will display UPS OFF for a few seconds.
z
In emergency situations, the EPO located on the back of the unit should be used.
7.2 Button Operation
Please note the three operating buttons on the front panel:
1. (a). Push the “ ON/OFF ” button (at least 3 seconds) to turn on the UPS.
(b). When UPS is working, push the “ON/OFF” button (at least 3 seconds) to turn off the
UPS.
2. Use “Enter” button to check content of UPS and the method is listed below:
(a). Push the “ENTER” button (at least 2 seconds) to check content of UPS. Each
content can be displayed by pressing at once, and it has
fifteen kinds of function to be
checked.