21 

UPS configurations 

1.

 

Various settings that have been chosen are shown in the UPS setting display. 

2.

 

To enter configuration mode, press the “FUNC” button for one second. The first 
configuration parameter will be shown on the LCD display. 

3.

 

Press the “FUNC” button to scroll through the parameters. 

4.

 

Press the “ENTER” button to select the parameter. 

5.

 

Press the “FUNC” button to scroll through the options for the selected parameter; Press   
the “ENTER” button to select the option. 

You may be prompted to save the selection, if so press the “ENTER” button to either 
confirm or save your selection. Other options are saved and started automatically. See 
the table below for further details. 

6.

 

If no buttons are pressed (or user inactivity) for ten seconds, the UPS shall exit the 
configuration mode and return to normal mode displaying Line mode. 

Caution! 

The factory default settings do not necessarily have to be changed, although 
you are free to tailor the UPS to your specific needs. 

 

22

 

Settings 

LCD 
display 

Explanation Selection 

Factory 
default 

208/220/230/240 V 

230V 

Output Volt. Setting

O/P V 
Setting 

Select Nominal Voltage 

100/110/115/120/127 V 

120V 

Input/Frequency I/P 

Setting

Select input frequency 
range when UPS goes into 
free run mode 

±2% 
±5% 
±7% 

±5% 

Input/Bypass 
Voltage 

I/P Bypass 
Set 

Select Input Voltage range 
when bypass is available 

±10% 
+10/-15% 
+15/-20% 

+10/-15% 

Free Run Mode 

Free Run 
Set

 

Select if UPS can run in 
Free run mode 
(unsynchronized) 

ON/OFF ON 

Bypass 
Enable/Disable at 
Free run mode 

Bypass 
disable 

If Enable is chosen, the 
UPS can go to bypass when 
unsynchronized. 

Disable/Enable Disable 

HE mode Setting 

HE Mode 
Set 

Select if UPS runs in high 
efficiency mode 

ON/OFF OFF 

Force Manual 
Bypass 

Manual 
bypass 

Permanently force UPS to 
bypass. For service only.**

ON/OFF

 

OFF 

Management of 
Load groups 

Outlet 
Setting 

You can put the two load 
groups on and off form 
front panel 

1 ON & 2 ON 
1 OFF & 2 ON 
1OFF & 2 OFF 
1 ON & 2 OFF

 

Both load 
segments 
ON 

Do Battery Test 

Battery Test

Detect battery is normal or 
not. 

 

 

Silence Function 

Silence Set

Enable or disable silence 
function 

ON/OFF

 

OFF 

Number of 
External battery 
Packs 

Bat Cabinet 
Set 

This setting is needed 
For UPS to predict 
Backup time 

0 (only internal batteries) 
1(one external cabinet) 
2 (two external cabinets)

 

Site wiring alarm 

Sit Fault Set

You can enable or disable 
the site wiring alarm 

Enable /Disable

 

Disable 

Select Language 

Language 

Select load language 

English, German, French, 
Spanish, Italian. 

English 

Set Generator Mode Generator 

Set unit in generator mode. 
*** 

ON/OFF OFF 

Set RS232 
communication 

RS232 
Control 

Set RS232 communication 
enable or disable 

Enable/Disable Enable 

 

Содержание DS1000B

Страница 1: ...User s Guide Durable Series Models DS1000B 1500B 2000B 3000B DS1000B RM 1500B RM 2000B RM 3000B RM ...

Страница 2: ... local branch offices or your dealers Who the warranty protects This warranty is valid only for the first consumer purchaser What the warranty does not cover 1 Any product on which the serial number has been defaced modified or removed 2 Damage deterioration or malfunction resulting from a Accident misuse neglect fire water or other acts of nature unauthorized product modification or failure to fo...

Страница 3: ...lusion of incidental or consequential damages so the above limitations and exclusions may not apply to you Limitations of Warranty for Australian States and Territories The Trade Practices Act 1974 and corresponding State and Territory Fair Trading Acts or legalization of another Government the relevant acts in certain circumstances imply mandatory conditions and warranties which cannot be exclude...

Страница 4: ... classe B respecte toutes les ٛ aterielٛ s du Reglement sur le ٛ ateriel brouilleur du Canada Declaration of Conformity Request Units labeled with a CE mark comply with the following standards and directives z Harmonic Standards EN 50091 1 1 and EN 50091 2 z EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC ...

Страница 5: ...el away from batteries 2 The instructions contained within this safety manual are deemed important and should be closely followed at all times during installation and follow up maintenance of the UPS and batteries CAUTION The unit has a dangerous amount of voltage If the UPS indicator is on the unit s outlets may have a dangerous amount of voltage even when not plugged into the wall outlet because...

Страница 6: ...hat a power failure lasts longer than a UPS backup time it will shut down avoiding battery discharge and as soon as voltage comes back the UPS will automatically charge up and start recharging the batteries As shown in fig 1 block diagram z An input filter reduces transients on the mains z For maintaining full battery charge AC power is rectified and regulated in the rectifier feeding power to the...

Страница 7: ... 3000VA 5 min 4 hours Additional External Battery Cabinets are available if more back up time is needed 6 3 Safety Information Information presented here is vital to all personnel and please also read the UPS safety manual Storage and Transportation Please handle with extreme caution since a high amount of energy is contained with the batteries Always keep the unit in position as marked on the pac...

Страница 8: ...mber the following when locating the UPS system and battery options z Avoid extremes of temperature and humidity Maximal battery life can be attained with a recommended temperature range of 15 C to 25 C z Provide protection for the equipment from moisture z Space and ventilation requirements must be met Ensure there is 100mm behind and 50mm on the sides of the UPS for ventilation z Ensure that the...

Страница 9: ...hased Installation with bottom bracket Part No RMB 06 2 PCS Screw M5 11 4 PCS Installation with rear bracket Part No RMB 01 2PCS Screw M5 11 4 PCS 10 5 2 Rear panel views 1KVA 1 5KVA Rear Panel SMART SLOT OPTIONAL DATA LINE PROTECTION BATTERY BACKUP OUTLETS EXTENDED BATTERY CONNECTOR USB SMART SLOT OPTIONAL DATA LINE PROTECTION BATTERY BACKUP OUTLETS EXTENDED BATTERY CONNECTOR USB 100 110 120V EPO...

Страница 10: ...CUIT BREAKER 12 RM 1U 1KVA Rear Panel RM 2U 1KVA 1 5KVA Rear Panel INPUT CIRCUIT BREAKER EPO RS232 SMART SLOT OPTIONAL BATTERY BACKUP OUTLETS 100 110 120V BATTERY BACKUP OUTLETS SMART SLOT 220 230 240V CIRCUIT BREAKER EPO RS232 INPUT USB INPUT USB RS232 CIRCUIT BREAKER EPO INPUT USB BATTERY BACKUP OUTLETS DATA LINE PROTECTION DATA LINE PROTECTION BATTERY BACKUP OUTLETS SMART SLOT SMART SLOT 100 11...

Страница 11: ...PS Connect a second battery cabinet to the first one with the cable provided if more than one is to be installed z Be aware of UPS parameters and changing the Battery pack quantity when using the external battery cabinets see chapter 7 2 z Connect the Input cable to the UPS and connect the other end to a grounded outlet The batteries will automatically charge when connected to the mains Please rea...

Страница 12: ...that allows you to install different communications cards It can be used parallel with either the RS232 or USB ports Currently there are two cards available for the optional interface slot An SNMP WEB card allows management and monitoring over a network or internet and the AS 400 card allows voltage free relay contacts Your local dealer will have more information about these option cards Connectin...

Страница 13: ...to chapter 5 2 regarding the two load segments that come with each model 18 7 User s guide to operations Necessary information for operation of the unit is covered in this chapter Normally the UPS runs automatically but on those few occasions such as just after installation all the starting and shutting down procedures are described herein 7 1 Starting and shutting down the UPS Starting the UPS z ...

Страница 14: ...YPASS While operating in bypass mode this LED will light up in yellow FAULT If any internal error occurs in the UPS this LED will light up in red and give off an audible alarm Press any of the buttons on the front panel to turn off the alarm 20 Status of the UPS measurements and alarms are all indicated on the LCD screen Figure 6 Control panel Normal display The UPS status is shown in normal displ...

Страница 15: ... goes into free run mode 2 5 7 5 Input Bypass Voltage I P Bypass Set Select Input Voltage range when bypass is available 10 10 15 15 20 10 15 Free Run Mode Free Run Set Select if UPS can run in Free run mode unsynchronized ON OFF ON Bypass Enable Disable at Free run mode Bypass disable If Enable is chosen the UPS can go to bypass when unsynchronized Disable Enable Disable HE mode Setting HE Mode S...

Страница 16: ... What You Should Do Output Overload Two Beeps per second The UPS is overloaded in Line Mode Your equipment needs more power than the UPS can provide The UPS operates on bypass Shut off the least important equipment connected to the UPS If this solves the overload problem the UPS will switch from bypass back to normal operation Battery Test No Beeps The UPS is doing a battery test No action needed ...

Страница 17: ... burn from high short circuit currents Please observe the following precautions 1 Remove jewelry and metal objects such as watches and rings 2 Use tools that have insulated handles 3 Keep tools and other metal objects from contacting and away from the batteries ELECTRIC ENERGY HAZARD Do not attempt to rewire alter or change any battery wiring or connectors Attempting to make such alterations can c...

Страница 18: ...ss Voltage 184 265 VAC user selectable 28 Input Voltage range 120 140 160 VAC 276 VAC Frequency 50 60 Hz Auto selection Frequency window from mains 45 65 Hz Synchronization window 3Hz Input current 1000 VA 4A 1500 VA 6A 2000 VA 7 7A 3000 VA 12A Input Power factor 0 97 OUTPUT Output Voltage 208 220 230 240 VAC selectable from LCD panel Voltage regulation 2 Voltage distortion 5 THD at full non linea...

Страница 19: ...oling Forced air cooling Humidity 0 95 non condensing Audible noise 40 db normal and battery mode 30 STANDARDS Safety EN50091 1 1 Emissions EN50091 2 class B Immunity EN50091 2 100 110 120V Model OUTPUT POWER 1000VA 700W 1500VA 1050W 2000VA 1400W 3000VA 2100W Connection Input Attached power cord Connection Output 6 x 5 15R US 6 x 5 15R US 12 x 5 15R US 12 x 5 15R US Battery type Lead acid 7 2Ah 12...

Страница 20: ...to 90 4 hours to 90 4 hours to 90 Dimensions W x L x H mm 428 x 425 x 84 428 x 425 x 84 428 x 635 x 84 428 x 635 x 84 Weight kg 17 1 18 1 31 6 32 5 19 Rack mount Model 1U OUTPUT POWER 1000VA 700W Connection Input IEC 320 10A Connection Output 4 x IEC 320 10A Battery type Lead acid 7 Ah 6V Number of batteries 4 Backup time full load 6 min Recharge time 4 hours to 90 Dimensions W x L x H mm 428 x 52...

Отзывы: