5-8
B-11: Set Days Between EQU
This constant is only displayed if Flooded is selected as battery type (B-02). Use
Constant B-11 to select the number of days between equalization charges. The
factory setting is OFF.
B-12: Manual Equalize
This constant is only displayed if Flooded is selected as battery type (B-02). Use
Constant B-12 to choose between manual and automatic equalization settings.
Press ENTER key to select Yes for manual equalization and then it will display
the Equalize voltage set in B-09 and the Max. EQU time set in B-10. Press
ENTER key again to start the manual equalization.
During equalization, only ESC key is active to leave the equalization process
screen.
After the manual equalization starts, BAT displays Battery voltage. Battery
temperature and Equalizing blinks in return. CHARGE displays charging current.
Finally, the remaining time for equalization charge is counted down.
WARNING: Before the manual equalization is selected, OPTI-Solar SC MPPT Series
should be connected to Battery Temperature Sensor (BTS-3). If it is not connected to
BTS-3, “Warning, Bat. Sr Not Connected” is displayed.
Press ESC key to select No to return to the display of Group B.
Group C
MPPT Setup
C-01: Set MPPT Type
Use Constant C-01 to set up the MPPT type: P and O, Scan and Hold, Percentage,
Hold Input V. The factory setting is P and O.
C-02: Set Scan Frequency
This constant is only displayed if P and O or Scan and Hold is selected as MPPT
Содержание SC-160X MPPT
Страница 7: ...VII Dimension for SC 50 MPPT Unit mm Fig 1...
Страница 8: ...VIII Dimension for SC 80 MPPT Dimension for SC 80X MPPT Unit mm Fig 2...
Страница 9: ...IX Dimension for SC 160X MPPT Unit mm Fig 3...
Страница 12: ...1 3 Fig 4...
Страница 20: ...3 2 3 2 The following is the Initialization Stage Flow Chart OTPI Solar SC 80 MPPT V0 9311...
Страница 22: ...3 4 3 3 The following is the Operation Stage Flow Chart Main Menu Main Menu Operation Menu Constants...
Страница 27: ...3 9 Main Menu Programming Group F Menu Group Constants Constants Edit Data Enter...
Страница 28: ...3 10 Main Menu Programming Group O Menu Group Constants Constants Edit Data Enter...
Страница 29: ...3 11 Main Menu Data Log Menu Constants Constants Edit Data Enter...