background image

- 7 -

Troubleshooting list

7

7-1 "No Action" on the transmitter or receiver after power has been applied.

7-2 "No Action" on alarm zone even though the beams are completely blocked.

START

Check to see that power

wires are properly 

connected and polarity is

correct.

Check to see that the 

input power is within  

10.5 to 28 VDC.

Call a technical support.

Disconnect the power wires from the power supply and

the photoelectric beam and test for short or open circuit.

Also test for short circuit to ground.

Repair as required.

OK

OK

Correct terminal 

connection and/or 

polarity.

Does the power supply

output more than

12 VDC?

There is a possibility that 

the power wires has been

cut.

Remove the power wires

from the power supply’s

output terminals.

Measure the voltage.

Does the power now

satisfy the requirement?

The power wires may be too long for the gauge being 

used. This will cause the voltage to drop. Use heavier wire

or use additional power supplies closer to the farthest unit.

If you are unsure of the proper wire gauge, call a technical

support.

The power wire is short circuited or grounded.

Repair as required.

The power supply may be malfunctioning. Repair is 

required, or call the power supply manufacturer.

Yes

YES

NG

NG

NO

NO

START

The alarm indicator LED 

lights but the control 

panel does not recognize 

the alarm signal.

Remove the alarm circuit 

wires from the receiver. 

Check the action of the

alarm output relay. Does 

the relay open when the

LED indicator activates?

The control panel may 

be malfunctioning, call 

the control panel 

manufacturer.

OK

OK

Change the layout of 

the beam, or call a 

technical support 

for further advice.

If the beam is interrupted 

at a location far from the 

receiver, no alarm signal 

is generated, but when 

the beam is interrupted

at a location near the 

receiver, an alarm signal

is generated.

Remove the alarm 

circuit wire from the 

receiver, and check for 

short circuits on the wires.

When the receiver’s 

cover is removed and 

the beems are blocked, 

the alarm indicator LED 

does not light.

Adjust vertical and/or horizontal alignment in order to move

the IR energy off of the reflective surface. Monitor the beam

strength (monitor jack) while adjusting beam to insure 

stable alignment.

The unit may be affected by electrical noise. 

May need to use shielded wires and/or metalic conduit

pipe. Call a technical support if you are unsure of the 

proper shielding techniques.

YES

NG

NO

NO

Is the control panel 

zone’s "loop response 

time" set to within 1 

second?

Call a technical support.

Re-wiring of the alarm 

circuit wire is required. 

Replace or repair 

as necessary.

Re-program the zone’s

“loop response time” 

appropriately.

Are there any other

outdoor beams near the

installation site?

Remove power from all

other transmitters and

conduct a walk test.

OK

NG

NO

YES

YES

Check other items.

Does the photoelectric 

beam work properly?

The receiver may be 

affected by other beam 

transmitters, or the 

beams are being 

reflected off of a shiny

surface.

Call a technical support.

Are there any surface 

between the transmitter

and the receiver that are

reflecting the beam?

When the lens of the 

receiver are completely 

covered, an alarm 

signal is generated.

Remove the alarm circuit 

wire from the receiver, 

place a voltmeter on the 

resistance, and measure 

the alarm output relay. 

Does the relay open

when power is removed?

The beam interruption 

time is set too long.

Turn the inturruption time adjustment dial 

counter-clockwise one graduation.

.

The intended target does

not block both the upper 

and the lower beams 

completely.

Does the receiver work when both the upper and the lower 

beams are completely blocked? If so, the mounting height

 is not proper. Adjust the mounting height.

NO

OK

NG

NO

YES

Содержание AX-330PLUS

Страница 1: ...N 1 1 1 BEFORE YOUR OPERATION Failure to follow the instructions provided with this indication and improper handling may cause death or serious injury Failure to follow the instructions provided with...

Страница 2: ...p of the pole Avoid aerial wiring For indoor application the wiring installation is similar to that of telephone wirings or the Internet For outdoor application use wire conduit as far as possible Som...

Страница 3: ...ng in Section 2 3 Dig out a hole on the right side of the rubber bushing marked with when it is need for the second wire Pull the wires through the wiring holes of the unit base Connect the unit base...

Страница 4: ...gth is obtained by dividing the maximum wire length listed right by the number of units a detector a receiver or a transmitter The power wire should not exceed that 350 msec Walk slow COM N C N O SP T...

Страница 5: ...comparing the measured voltage values with the parameter values in the following table To obtain an excellent alignment level the measured voltage value must be greater than 3 0V Remember to obtain t...

Страница 6: ...Tamper switch Operating temperature Environment humidity Alignment angle Installation Weight Transmitter Receiver AX 330PLUS Infrared photoelectric 100 m 330 ft 1 000 m 3 300 ft Pulsed infrared 50 to...

Страница 7: ...terrupted at a location near the receiver an alarm signal is generated Remove the alarm circuit wire from the receiver and check for short circuits on the wires When the receiver s cover is removed an...

Страница 8: ...uirement Completed Remove any objects or move the beams Go to 7 1 on the previous page OK OK NO NG NG NG START Check alignment voltage from the monitor jack Does it satisfy the minimum requirement Rem...

Отзывы: