Biopel MINI - Installation and Operation Instructions 

29 

5.9 Lambda 1% 

Required O

2

 in % for minimum boiler power. Therefore, the boiler control unit is able to 

maintain the required oxygen in the boiler within 1 - 1% of the set value. We are also 

talking about the average value of oxygen maintained in the boiler throughout its 

operation. 

Short-term deviations of oxygen from the set value are perfectly normal due to external 

factors such as changes in chimney draft, cleaning the burner by increasing the fan speed 

(Burner Cleaning function in the Main Settings), etc. 

According 

to the 

burner 

size. 

* Connecting the Lambda probe to one of the RS data outputs in the control unit. 

 

6. De-ashing * 

Activating the motor that drives the worm that empties the ash from the boiler into an 

external container. Extends the requirement for manual cleaning of the boiler. 

 

6.1 Operating time 

The operating time of the motor that drives the ash removal worm. We recommend to 

set it between 5-20min, depending on the amount of ash generated. The larger the 

burner, the longer the cleaning time. 

5-20min 

6.2 Pause time 

For how long the motor is in a stand-by before reactivation occurs. This depends on the 

pellet quality and burner size. The recommended setting is anything between 2-20 

hours. 

2-20h 

* Connecting the Ash Remover to the "De-ashing" output on the control unit. 

 

7. Compressor cleaning 1, 

2, 3 *

2

 

Cleaning the burner and boiler exchanger with the compressor set. 

On state 

Off state 

7.1 ON 

In the on state, the compressor always cleans after the extinction phase 

and also during PID operation according to the time set in the Pause Time 

function. After cleaning during PID mode, the light is lost (the photosensor 

does not detect the flame) and the boiler goes into Ignition after the set 

time. This time is the 20s without flame set in the Service menu, in the 

Operation Check function. 

On 

 

7.2 OFF 

When disabled, the compressor only cleans after extinction and does not 

clean during PID mode. 

 

Off 

7.3 Cleaning time 

The compressor's total cleaning time. Recommended between 1-3 min. 

Bigger burner, longer cleaning time. During this time, the solenoid valve 

opens and closes periodically according to the values set in the Open Time 

and Cycle Time functions. 

When set to On, it is necessary to complete the total Cleaning Time before 

the automatic ignition occurs so that the compressor does not blow the 
pellet dose for automatic ignition. Therefore, set the Cleaning Time to a 

maximum of 1min. 

1min 

3min 

7.4 Opening time 

Opening of the solenoid valve. Time of one cleaning period. 

We recommend between 1-2s. 

2s 

2s 

7.5 Cycle time 

The time required to re-pressurise the compressor so that the valve can be 

reopened and cleaned again. We recommend 20s. 

25s 

20s 

7.6 Pause time 

The time of pause between cleaning. Recommended between 10-20 hours. 

This time is only valid when cleaning during PID operation, i.e., when the 

compressor is ON. 

10-24h 

Not taken 

into 

account*

1

 

* Compressor in the Off setting works only after the Extinction phase (in Off state). Therefore, we do not consider the Pause Time. 
* Connecting the compressor solenoid valve to one of the "Compressor 1, 2 or 2" outputs in the control unit. 

 

 

8. Built-in valve 1, 2 *

1

 

Controls the mixing valve for one heating circuit. 

 

8.1 Switch off the valve 

Deactivate the mixing valve if you do not want to use it at that moment. 

8.2 Switch on the valve 

Activating the mixing valve. 

8.3 Set valve temperature 

*

2

 

Enter the desired temperature to be maintained by the mixing valve. The maximum 

adjustable temperature on the mixing valve is determined by the Mixing Valve Type 

function. 

Optional 

Содержание Biopel MINI

Страница 1: ...tended to both installers and end customers The individual chapters are presented chronologically staring with boiler installation start up and proper set up to the regular use and maintenance Read al...

Страница 2: ...rnal feeder 18 6 4 Control unit 19 6 5 Electrical Connection of Accessories 20 7 BOILER CONTROL UNIT 23 7 1 Basic navigation 23 7 2 Basic operating modes 24 8 CONTROL UNIT FUNCTIONS DESCRIPTION 25 8 1...

Страница 3: ...MWARE UPDATES 47 16 OPERATING AND ALARM MESSAGES 47 17 TROUBLESHOOTING OF SPECIFIC SITUATIONS 48 18 FACTORY SETTINGS 52 19 ENERGY EFFICIENCY 54 20 IDENTIFICATION MARKS 55 21 WARRANTY CONDITIONS GENERA...

Страница 4: ...valve pump 2 pump with independently configurable settings Equithermal control based on outdoor temperature Time control of boiler outlet temperature programmable weekly operation mode Heating of stor...

Страница 5: ...el wood pellets 6 8mm Fuel consumption at boiler nominal output kg h 2 36 3 36 4 68 6 52 8 42 Fuel consumption at boiler minimal output kg h 0 77 1 01 1 38 1 96 2 64 Emission class 1 5 Ecodesign Effic...

Страница 6: ...iopel Mini 15 Biopel Mini 21 Biopel Mini 30 Biopel Mini 40 Boiler depth including burner cover H mm 1043 1170 Height of burner cover I mm 349 413 Burner cover depth J mm 281 308 1 Emission values and...

Страница 7: ...2 35 0 36 Flow resistance coefficient 1 21 0 46 t 20 C Water flow through the boiler m3 h 0 907 0 004 Boiler s hydraulic loss Pa 62 24 Boiler s hydraulic loss mbar 0 62 0 24 Flow resistance coefficien...

Страница 8: ...5 111 5 120 139 139 J 108 5 108 5 120 139 139 K 53 53 50 4 58 5 58 5 3 4 Hopper Hoppers are divided into 2 main types Compact version and external version applicable for all boiler sizes In the boiler...

Страница 9: ...overs you will find a hole for attaching the automatic exchanger cleaner an additional device and ducts leading the wiring from the unit to the rear of the boiler There are 2 inlets and outlets in the...

Страница 10: ...to change them at regular intervals The ignition cartridge ensures automatic ignition of pellets which normally takes 3 to 5 minutes The resulting flame is detected by a photosensor which ensures the...

Страница 11: ...erted d Cleaning hole for removing dust out of the hopper e Filling opening can be fitted with a cover f Compact hopper g Hole for changing the feeder to the other side h Cleaning hole for removing du...

Страница 12: ...he boiler from the front of the boiler Before installing the burner it is necessary to first select the side to open the door If you want the door to open on the opposite side then the door must be re...

Страница 13: ...npack the hopper from the slatting remove the protective film and place the hopper next to the boiler Check the ash door opening If the hopper is on the side of the boiler with the ash door hinges you...

Страница 14: ...turn it so that the feeder opening faces the burner After inserting the feeder into the chimney then re adjust the hopper and feeder position so that the feeder outlet is above the burner Attach the...

Страница 15: ...ws After loosening the screws then pulling backwards and then upwards carefully remove the orange cover and pull the feeder cable through to the rear of the boiler as shown in the picture Caution Ther...

Страница 16: ...he hopper and damaging the PVC burner hose Place the display in the display holder according to the pictures above Adjust the display cable so that the excess length is inserted under the orange boile...

Страница 17: ...components For complete boiler exchanger cleaning remove the Tower container empty pellets and clean the boiler exchanger properly and completely every now and then The intervals for cleaning vary an...

Страница 18: ...end of the PVC tube must not be deformed in any way The edges of the tube opening must be horizontal with the tube body not curved inwards towards the worm shaft If this were the case there would be...

Страница 19: ...d place the top cover back on the boiler and you start the boiler for the first time using the main switch red button on top of the boiler The installation is practically complete at this point This i...

Страница 20: ...ssories connection Additional sensor 2 United output for C2 C1 Additional sensor 1 Solar contact Outdoor sensor United output outdoor and return sensor Return water sensor Valve sensor 2 United output...

Страница 21: ...n menu Built in valve 1 and 2 Equitherm control Outdoor temperature correction Firing up blocked Return water sensor Installation menu Built in valve 1 and 2 Return flow protection Valve sensor 2 and...

Страница 22: ...pause and Minimum feeder operation Pellet Settings Operating parameters Maximum power Minimum feeder pause and Maximum feeder operation Installation menu Coefficients Min feeder coefficient and Max f...

Страница 23: ...ol unit main panel a CH temperature measured by CH sensor connected to the sink on the outlet at the back of the boiler b Selected CH temperature set in the unit s Main Menu Standard 65 80 C c The boi...

Страница 24: ...flame is not smothered by a large amount of pellets after ignition FS 1 50 of maximum output depending on boiler type Max output the boiler gradually increases its output up to the maximum i e 100 Th...

Страница 25: ...Set DHW temperature Select the desired domestic hot water temperature DHW is only activated if the DHW sensor is connected to the DHW sensor output in the external socket and if the operating mode in...

Страница 26: ...urer s screen Display for the installer 9 2 1 2 Display brightness Change display brightness for its better visibility 9 3 Display saving mode Select the brightness during the display power saving mod...

Страница 27: ...r content Enter the size of the pellet container The main panel then displays how much fuel is left in the container 2 3 Fuel weight Enter the amount of pellets in grams weighed using the Start weighi...

Страница 28: ...he longer the time must be 3 5min 5 3 Oxygen surge Correction factor for pellet dosing in How big is 1 regulation intervention to the pellet feed The regulation will be according to the set time in th...

Страница 29: ...detect the flame and the boiler goes into Ignition after the set time This time is the 20s without flame set in the Service menu in the Operation Check function On 7 2 OFF When disabled the compresso...

Страница 30: ...door temperature measured by the outdoor sensor The temperature at the valve will be automatically adjusted according to the set values Optional 8 11 Room thermostat Activate the control of the mixing...

Страница 31: ...pump is switched on above the set temperature Linked to the boiler protection function 8 17 4 Temperature On Set pump switch on temperature Linked to the Switched over limit function 8 18 Factory sett...

Страница 32: ...Reverse flow sensor Reverse water flow sensor connected to the Return sensor output 11 4 Equithermal sensor Equithermal sensor connected to the Weather sensor output 11 4 8 Additional sensor 1 Additio...

Страница 33: ...er If the temperature does not exceed the set limit in the interval set in the Waiting Time function the next boiler is switched on 14 5 3 Boiler 3 switch on temperature Temperature at which the boile...

Страница 34: ...emperature than the set temperature will force the boiler to shut down Caution Do not forget to calibrate the Outdoor Sensor if it does not measure correctly in the Outdoor Temperature Correction func...

Страница 35: ...not occur the external feeder will feed half the pellet load set in Feeding Time and try two ignitions If there is no flame during the time set in this function an error message occurs and the boiler...

Страница 36: ...n the pellets quickly but we do not want the fan speed to be too high which would cause unburned pellets to fall into the ashtray 50 80 1 3 2 Feeding time Operation of the internal feeder in the burne...

Страница 37: ...60 C DHW Hysteresis 10 C The DHW pump valve will be reactivated automatically when the DHW temperature drops below 50 C 5 10 C 15 Disinfection Forced increase in DHW temperature to destroy bacteria i...

Страница 38: ...from the feeder into the burner Setting the CH temperature and modulation range CH temperature i e the boiler power temperature should be as high as possible preferably between 65 and 80 C The follow...

Страница 39: ...ation wait a few minutes until the main panel displays the maximum power in kW set during First Start up and 100 fan speed At this point the boiler is operating at full power Open the ash door careful...

Страница 40: ...rnal Feeder type with the correct motor speed 45 angle of the External Feeder from the ground Chimney draft 15Pa Size and type of pellets We then recommend that you measure the External Feeder power b...

Страница 41: ...hat no colder water than the actual DHW boiler temperature enters the DHW boiler When the set DHW temperature is reached the DHW pump is switched off and the CH pump is activated at the same time to e...

Страница 42: ...cooled water in the system to heat up again The boiler will heat the DHW even if there is no requirement for central heating from the room thermostat 11 2 Two CH circuit DHW Connection with two centra...

Страница 43: ...DHW pump will only be switched on if the current measured CH temperature is higher than the current measured DHW temperature This is to ensure that no colder water than the actual DHW boiler temperatu...

Страница 44: ...ating the boiler if the pump is switched off together with the boiler o Lowering the CH Set Temperature using the thermostat Deactivate the Ignition function in the Installation Menu Room Thermostat S...

Страница 45: ...ain Panel top left the DHW priority message is now displayed o Note that the DHW pump will only be switched on if the current measured CH temperature is higher than the current measured DHW temperatur...

Страница 46: ...cleaning burner grate cleaning boiler exchanger cleaning combustion check photosensor cleaning door tightness check complete burner cleaning feeder cleaning hopper cleaning Flue gas outlet and chimne...

Страница 47: ...ternet OPOP spol s r o technicians are ready to deal with any questions you may have 15 FIRMWARE UPDATES Each v9 MINI unit can be updated using a USB key OPOP spol s r o regularly releases new version...

Страница 48: ...as been switched off by reaching the CH temperature 14 Message DHW heated DHW temperature has been reached The DHW pump has been switched off 15 Alarm Outdoor sensor failure The outdoor temperature se...

Страница 49: ...ing pause set a longer feeding pause time d Reduce air quantity Service menu Feeder settings Work i Min fan speed operation set a lower number e Increase air quantity Service menu Feeder settings Work...

Страница 50: ...combustion air then it means that the Lambda sensor is measuring a large amount of excess air and trying to reduce it to the set limit by adding fuel or reducing fan speed b This could be due to a lea...

Страница 51: ...her f Wrong grate position in the burner clogged burner grate holes g Lower than required chimney draft h Large amount of dust in the pellets 14 High temperature of the internal feeder in the burner a...

Страница 52: ...kW 30kW 40kW Fan speed 70 70 70 70 70 Feeding time 5s 5s 5s 5s 5s Feeding pause 20s 20s 20s 20s 20s Extinction time 10min 10min 10min 10min 10min Delay time 5min 5min 5min 5min 5min Service menu 11kW...

Страница 53: ...0h 10h 10h Installation menu Compressor 2 and 3 exchanger 11kW 15kW 21kW 30kW 40kW Cleaning period 1min 1min 1min 2min 2min Opening time 3s 3s 3s 3s 3s Cycle time 25s 25s 25s 25s 25s Pause time 8h 8h...

Страница 54: ...plier supplier s model identification mark energy efficiency class nominal thermal power in kW energy efficiency index seasonal heating energy efficiency in OPOP s r o Biopel 11 A 11 116 79 OPOP s r o...

Страница 55: ...of biomass 30 70 and fossil fuels no no Other mixture of biomass and fossil fuels no no Properties when operating with preferred fuel Seasonal indoor heating energy efficiency s 79 Energy Efficiency I...

Страница 56: ...30 70 and fossil fuels no no Other mixture of biomass and fossil fuels no no Properties when operating with preferred fuel Seasonal indoor heating energy efficiency s 79 Energy Efficiency Index EEI 11...

Страница 57: ...30 70 and fossil fuels no no Other mixture of biomass and fossil fuels no no Properties when operating with preferred fuel Seasonal indoor heating energy efficiency s 80 Energy Efficiency Index EEI 11...

Страница 58: ...30 70 and fossil fuels no no Other mixture of biomass and fossil fuels no no Properties when operating with preferred fuel Seasonal indoor heating energy efficiency s 81 Energy Efficiency Index EEI 11...

Страница 59: ...30 70 and fossil fuels no no Other mixture of biomass and fossil fuels no no Properties when operating with preferred fuel Seasonal indoor heating energy efficiency s 82 Energy Efficiency Index EEI 12...

Страница 60: ...y dust and moisture in pellets chimney draft or correct combustion settings 16 It is forbidden to use flammable liquids petrol alcohol etc to fire the boiler 17 It is forbidden to overheat the boiler...

Страница 61: ...ns Internal wiring SN 33 2180 Electrical regulations Connection of electrical devices and appliances SN 34 0350 Electrical regulations Regulations for mobile connections and wiring management SN 33 60...

Страница 62: ...ate the circumstances under which the defect occurred The method and place of repair will be decided by our company We guarantee the permanent tightness of the steel weldment for a standard period of...

Страница 63: ...he safety valve used up to a maximum of 2 bar Is the return water temperature during boiler operation 55 C or more Is a 3 way or 4 way valve used as protection against low temperature corrosion Is the...

Страница 64: ...757 01 Vala sk Mezi Bank account Komer n banka a s Account number 1608851 0100 Business ID No 47674105 Tax ID No CZ 47674105 Telephone Sales Department 571 675 589 secretariat 571 611 250 Production...

Отзывы: