- 21 -
5. panel indicator status is as
the right figure:
(1)
UPS running status
Utility power is normal and
it converts to utility mode.
UPS don’t start up if didn’t
press the “ON” button down
on the UPS panel.
(2)
Handling way:
Please deal with it refer to status dealing flow Chart 2.
6. panel indicator status is as
the right figure:
(1)
UPS running status:
Utility supplies power. Under
overload 125%, overload
indicator is lit on and the
buzzer long beeps.
(2)
Handing way:
Please remove load to ensure
the percent of LCD output
power indicated is below 100%.
If the problem still presents after removing load, please refer to flow
Chart 3 of status handling.
Figure 26
Figure 27