- 12 -
6.
Please connect power correctly
Simple identification way to power polarity:
(1)
Line (L): There is 220V relative to other two holes.
(2)
Neutral (N): there is 220V relative to the Line, there is 0.5-2V
relative to the ground.
(Load current circulate through neutral)
(3)
Ground (G): Please find out correct connecting point to the ground
in the switchboard.
7.
If the difference between the neutral and the ground is more than 5V
or it can’t meet the requirement of system, please reinstall good
grounding system to keep safety of system operation.
8.
The comparison list of input current rating and input cable size is as
follows:
Model Max.
input current
Input wire
Terminal specification
Online UPS PP1KL
5A
12AWG
5.5~6
Online UPS PP2KL
10A
10AWG
5.5~6
Online UPS PP3KL
15A
10AWG
5.5~6
Online UPS PP4KL
20A
10AWG
5.5~6
Online UPS PP5KL
25A
10AWG
5.5~6
Online UPS PP6KL
30A
10AWG
5.5~6
Online UPS PP8KL
40A
8AWG
8.5~8
Online UPS PP10KL
50A
8AWG
8.5~8
Online UPS PP12KL
60A
5AWG
16~8
Online UPS PP15KL
75A
5AWG
16~8
9.
The power cable and the impaction terminal must be first grade
product manufactured by authentic manufacturer. Prohibit use spent
and inferior product.
10.
The power cable must be impacted by impaction terminal of authentic
manufacturer, prohibit directly wrapping power cable to the terminal
plate.
11.
After fastening input cable, please see if the input cable contacts with
protection cover and avoid short-circuit.
12.
Please turn off power when connecting cable, prohibit operation on
Содержание PP10KL
Страница 1: ...Online UPS PP1 15KL User Manual ...
Страница 11: ... 8 ...
Страница 14: ... 11 ...
Страница 27: ... 24 Flow chart 1 of status handing ...
Страница 28: ... 25 Flow chart 2 of status handing ...
Страница 29: ... 26 Flow chart 3 of status handing Flow chart 3 of status handing ...
Страница 30: ... 27 Flow chart 4 of status handing ...