- 18 -
5.
Utility indicator will be lit on when UPS input power source is
resumed. Press the LCD display cycle switch button to switch items
displayed, inspect if the display value is normal, thus first startup
procedure has been completed. Please measure output voltage and see
if it meets the requirement, then connect load to UPS output terminal.
Use pure power provided by UPS.
6.
After connect load, press LCD display cycle switch button to switch
items displayed till display the output power display percent %. If the
value displayed is more than 100%, please dismantle the unimportant
load till the value displayed is less than 100%.
5.3
Operation process for routine turn-off
If you want to switch on/off UPS when daily using, please operate UPS
according to the following ways:
1.
You can switch off UPS by pressing the “OFF’ button on front panel.
At the time UPS is on bypass mode, output is utility powered and the
batteries are charged.
2.
Always turn on UPS by pressing down the “ON” button when daily
operation.
5.4
Operation process for long-time no switch on/off
1.
If UPS is not used above ten days, please first turn off UPS by
pressing the “OFF” button on front panel, then switch the power
switch NFB on back panel to the position of “OFF”.
2.
If UPS is not used above three months, please run UPS for above 24
hours reference to the first start-up process and keep the battery the
full voltage level to extend battery life.
Содержание PP10KL
Страница 1: ...Online UPS PP1 15KL User Manual ...
Страница 11: ... 8 ...
Страница 14: ... 11 ...
Страница 27: ... 24 Flow chart 1 of status handing ...
Страница 28: ... 25 Flow chart 2 of status handing ...
Страница 29: ... 26 Flow chart 3 of status handing Flow chart 3 of status handing ...
Страница 30: ... 27 Flow chart 4 of status handing ...