7.1 MODBUS MEMORY MAP
Register
Address
Description
Register
Type
Data
Range
Over
Range
Read/Write
Comments
4
Reset User Defined
Volume Total
Coil
NA
NA
Read/Write
Turn coil ON (1) to reset total on F-4600
Turn coil to OFF (0)once reset is complete
7
Reset Aux Input Total -
Input 1
Coil
NA
NA
Read/Write
Turn coil ON (1) to reset total on F-4600
Turn coil to OFF (0)once reset is complete
8
Reset Aux Input Total -
Input 2
Coil
NA
NA
Read/Write
Turn coil ON (1) to reset total on F-4600
Turn coil to OFF (0)once reset is complete
9
Reset Aux Input Total -
Input 3
Coil
NA
NA
Read/Write
Turn coil ON (1) to reset total on F-4600
Turn coil to OFF (0)once reset is complete
10
Reset Aux Input Total -
All Inputs
Coil
NA
NA
Read/Write
Turn coil ON (1) to reset total on F-4600
Turn coil to OFF (0)once reset is complete
11
Aux Output 1
Coil
NA
NA
Read/Write
Turn coil ON (1) to latch Aux I/O # 1 closed. Turn
coil to OFF (0) to latch I/O # 1 open. Aux I/O #
1 must have been configured as an output at the
factory, and programmed for "MODBUS Coil" in
the commissioning menu.
12
Aux Output 2
Coil
NA
NA
Read/Write
Turn coil ON (1) to latch Aux I/O # 2 closed. Turn
coil to OFF (0) to latch I/O # 2 open. Aux I/O #
2 must have been configured as an output at the
factory, and programmed for "MODBUS Coil" in
the commissioning menu.
13
Aux Output 3
Coil
NA
NA
Read/Write
Turn coil ON (1) to latch Aux I/O # 3 closed. Turn
coil to OFF (0) to latch I/O # 3 open. Aux I/O #
3 must have been configured as an output at the
factory, and programmed for "MODBUS Coil" in
the commissioning menu.